Plan Review Notes For Permit 23050740 |
Permit Number |
23050740 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-07-20 12:38:02 | PLAN REVIEW COMMENTS | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE ANCHOR SPACING IS NOT SPECIFIED IN THE ACCORDION | | SHUTTER INSTALLATION SCHEDULE FOR OPENINGS 5,6,7 AND 8. | | FBC 107.2.1 | | |
|