Notes |
Date |
Text |
2023-06-21 14:12:37 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) 1) SUBMIT GENERATOR PAD DRAWINGS WITH GENERATOR TO | | PAD ANCHORING DETAILS. IF A PREFABRICATED GENERATOR PAD | | WILL BE USED, SUBMIT SIGNED AND SEALED SITE SPECIFIC | | ENGINEERING FOR IT. FBC AMENDMENTS 107.2.1 | | | | 2) THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10 | | FEET FROM ANY OPENINGS INTO A BUILDING. SPECIFY THIS ON | | THE SURVEY. FBC-R303.5.1 INTAKE OPENINGS. MECHANICAL | | AND GRAVITY OUTDOOR AIR INTAKE OPENINGS SHALL BE | | LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM ANY | | HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS, | | CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS | | AND LOADING DOCKS. | | |
|