2023-06-21 14:12:37PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) 1) SUBMIT GENERATOR PAD DRAWINGS WITH GENERATOR TO
 PAD ANCHORING DETAILS. IF A PREFABRICATED GENERATOR PAD
 WILL BE USED, SUBMIT SIGNED AND SEALED SITE SPECIFIC
 ENGINEERING FOR IT. FBC AMENDMENTS 107.2.1
  
 2) THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10
 FEET FROM ANY OPENINGS INTO A BUILDING. SPECIFY THIS ON
 THE SURVEY. FBC-R303.5.1 INTAKE OPENINGS. MECHANICAL
 AND GRAVITY OUTDOOR AIR INTAKE OPENINGS SHALL BE
 LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM ANY
 HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS,
 CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS
 AND LOADING DOCKS.
  