2023-05-18 11:22:51 | RESIDENTIAL(R2) RE-ROOF BUILDING REVIEW COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| |
| NOTE: |
| LEVEL 1 ALTERATION. SEC. 602 FBC-EXISTING BUILDING. |
| SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK SHALL |
| COMPLY WITH THE MATERIALS AND METHODS REQUIREMENTS IN |
| THE FLORIDA BUILDING CODE. |
| |
| 1- FLAT ROOF FLORIDA PRODUCT APPROVAL FL16709-R10 |
| SUBMITTED CAN NOT BE USED FOR THIS BUILDING. THIS |
| BUILDING IS LOCATED IN EXPOSURE D WITH A WIND SPEED OF |
| 170MPH. ACCORDING TO BASE SHEET ATTACHMENT SYSTEM ON |
| PAGE 25 OF 25 THIS PRODUCT APPROVAL CAN NOT BE USED FOR |
| ROOF ZONE #3. IT SAYS N/A FOR ROOF ZONE 3. |
| THE SUBMITTED ENGINEERING CALCULATIONS CAN NOT BE USED |
| EITHER BECAUSE THE PRODUCT APPROVAL DOESN'T ALLOW |
| ENHANCED FASTENING. |
| NEED TO PROVIDE PRODUCT APPROVAL WITH AN ASSEMBLY THAT |
| MEETS OR EXCEEDS THE DESIGN PRESSURES FOR ALL ROOF |
| ZONES OR THAT ALLOWS ENHANCED FASTENING. |
| F.A.C. 61G20.3.001. SEC. 1609.1 FBC-BUILDING. |
| |
| 2- ROOF TO WALL CONNECTIONS: |
| THE BUILDING HAS A VALUATION OF MORE THAN $300,000. |
| NEED TO COMPLY WITH THE ROOF TO WALL CONNECTIONS AS |
| REQUIRED BY SEC. 706.8 FBC-EXISTING BUILDING. |
| STORM ROOFING, INC LETTER SUBMITTED IS NOT ACCEPTABLE. |
| THE ESTIMATE FOR THE ROOF TO WALL EVALUATION AND |
| INSTALLATION OF CONNECTIONS AT GABLE ENDS OR ALL |
| CORNERS HAS TO BE DONE BY LICENSED GENERAL OR BUILDING |
| CONTRACTOR NOT BY ROOFING CONTRACTOR. |
| ANOTHER OPTION IS TO SHOW THAT THE EXISTING ROOF TO |
| WALL CONNECTIONS MEET OR EXCEED FLORIDA BUILDING CODE. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |
| [email protected] |