Plan Review Notes For Permit 23050674 |
Permit Number |
23050674 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2023-06-22 14:49:53 | JONATHAN BROOKS JR. | | BUILDING PLANS EXAMINER | | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM | | PHONE (561) 805-6656 | | EMAIL: [email protected] | | | | 1ST REVIEW: FBC 2020 7TH EDITION | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT | | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. | | | | 1. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL5259-R39 | | COVERS MULTIPLE ATTACHMENT LIMITATIONS. SELECTED | | ATTACHMENT LIMITATION SYSTEM USED FROM 5.8.3.2 | | MECHANICALLY-ATTACHED BASE SHEET TABLE 4A ALLOWABLE | | DESIGN PRESSURES, DIRECT-TO-DECK UNDERLAYMENT IN TILE | | ROOF APPLICATIONS SYSTEM NO. UDL-2 DO NOT ALLOW FOR THE | | USE OF 30# FELT AS A BASE PLY. SELECT A SYSTEM THAT | | MEETS THIS REQUIREMENT OR SELECT A 2-PLY UNDERLAYMENT | | SYSTEM FROM TABLE 4B. ALL APPLICABLE DETAILS AND | | ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT | | APPROVAL DRAWINGS. | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | |
|