2023-06-22 14:49:53JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL5259-R39
 COVERS MULTIPLE ATTACHMENT LIMITATIONS. SELECTED
 ATTACHMENT LIMITATION SYSTEM USED FROM 5.8.3.2
 MECHANICALLY-ATTACHED BASE SHEET TABLE 4A ALLOWABLE
 DESIGN PRESSURES, DIRECT-TO-DECK UNDERLAYMENT IN TILE
 ROOF APPLICATIONS SYSTEM NO. UDL-2 DO NOT ALLOW FOR THE
 USE OF 30# FELT AS A BASE PLY. SELECT A SYSTEM THAT
 MEETS THIS REQUIREMENT OR SELECT A 2-PLY UNDERLAYMENT
 SYSTEM FROM TABLE 4B. ALL APPLICABLE DETAILS AND
 ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT
 APPROVAL DRAWINGS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  