Plan Review Notes For Permit 23050569 |
Permit Number |
23050569 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-05-26 14:13:19 | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW | | | | 1. SIGN MUST BE CONTROLLED BY AN EXTERNALLY OPERABLE | | SWITCH OR CIRCUIT BREAKER THAT OPENS ALL UNGROUNDED | | CONDUCTORS. NEC 600.6 | | NOTE: THE DISCONNECTING MEANS MUST BE WITHIN SIGHT OF | | THE SIGN. NEC 600.6(A)(1) | | | | END OF COMMENTS | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | RUBEN P. PERDOMO, P.E. | | ELECTRICAL PLANS EXAMINER/ INSPECTOR | | 561-805-6738 | | [email protected] | | |
|