Plan Review Notes
Plan Review Notes For Permit 23050569
Permit Number 23050569
Review Stop E
Sequence Number 1
Notes
Date Text
2023-05-26 14:13:19FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. SIGN MUST BE CONTROLLED BY AN EXTERNALLY OPERABLE
 SWITCH OR CIRCUIT BREAKER THAT OPENS ALL UNGROUNDED
 CONDUCTORS. NEC 600.6
 NOTE: THE DISCONNECTING MEANS MUST BE WITHIN SIGHT OF
 THE SIGN. NEC 600.6(A)(1)
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 RUBEN P. PERDOMO, P.E.
 ELECTRICAL PLANS EXAMINER/ INSPECTOR