Plan Review Notes For Permit 23050498
Permit Number 23050498
Review Stop B
Sequence Number 2
Notes
Date Text
2023-06-22 13:34:46JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL1654-R31 SYSTEM NO. W-195 DOES NOT MEET THE
 MINIMUM ZONE 3 DESIGN PRESSURE REQUIREMENT OF -108.17
 FOR EXPOSURE CATEGORY C AREAS. PROVIDE SYSTEM THAT
 MEETS OR EXCEEDS ALL DESIGN PRESSURE REQUIREMENTS FOR
 EXPOSURE CATEGORY C/PROVIDE SIGNED AND SEALED
 ENGINEERED NAILING CALCULATIONS WITH AN APPROVED
 SYSTEM. PLEASE NOTE: FL1654-R31 WAS REVISED ON JUNE 20,
 2023 TO FL1654-R32. THE PRODUCT APPROVAL MUST BE
 SUBMITTED TO INCLUDE COVER PAGE(S), EVALUATION REPORT
 PAGES 1-5 & INSTALLATION INSTUCTIONS FOR THE SYSTEM TO
 BE USED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  