2023-06-02 11:53:17JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. SUBMITTED PRODUCT APPROVAL FL1654-R30 HAS BEEN
 REVISED TO FL1654-R31. PLEASE PROVIDE THE FOLLOWING:
 INCLUDE COVER PAGE, EVALUATION REPORT PAGES 1-5 AND
 INSTALLATION INSTRUCTIONS FOR SYSTEM USED. FLORIDA DBPR
 PRODUCT APPROVAL FL1654-R30 SYSTEM NO. W-209 DO NOT
 MEET THE MINIMUM ZONE 3 DESIGN PRESSURE REQUIREMENT OF
 -108.17 FOR EXPOSURE CATEGORY C AREAS. PROVIDE SYSTEM
 THAT MEETS OR EXCEEDS ALL DESIGN PRESSURE REQUIREMENTS
 FOR EXPOSURE CATEGORY C/PROVIDE SIGNED AND SEALED
 ENGINEERED NAILING CALCULATIONS WITH AN APPROVED
 SYSTEM. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE
 CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS.
 DETAILS AND ATTACHMENTS NOT SPECIFICALLY COVERED IN
 PRODUCT APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING.
 AS PER RULE 61G20-3.
 2. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF
 DIAGRAM/SKETCH AND INCLUDE FLAT ROOF SLOPE(S). FLAT/LOW
 SLOPE ROOFS MUST SHOW POSITIVE DRAINAGE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  