2023-06-02 11:53:17 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| PHONE (561) 805-6656 |
| EMAIL: [email protected] |
| |
| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| |
| 1. SUBMITTED PRODUCT APPROVAL FL1654-R30 HAS BEEN |
| REVISED TO FL1654-R31. PLEASE PROVIDE THE FOLLOWING: |
| INCLUDE COVER PAGE, EVALUATION REPORT PAGES 1-5 AND |
| INSTALLATION INSTRUCTIONS FOR SYSTEM USED. FLORIDA DBPR |
| PRODUCT APPROVAL FL1654-R30 SYSTEM NO. W-209 DO NOT |
| MEET THE MINIMUM ZONE 3 DESIGN PRESSURE REQUIREMENT OF |
| -108.17 FOR EXPOSURE CATEGORY C AREAS. PROVIDE SYSTEM |
| THAT MEETS OR EXCEEDS ALL DESIGN PRESSURE REQUIREMENTS |
| FOR EXPOSURE CATEGORY C/PROVIDE SIGNED AND SEALED |
| ENGINEERED NAILING CALCULATIONS WITH AN APPROVED |
| SYSTEM. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE |
| CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. |
| DETAILS AND ATTACHMENTS NOT SPECIFICALLY COVERED IN |
| PRODUCT APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. |
| AS PER RULE 61G20-3. |
| 2. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF |
| DIAGRAM/SKETCH AND INCLUDE FLAT ROOF SLOPE(S). FLAT/LOW |
| SLOPE ROOFS MUST SHOW POSITIVE DRAINAGE. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |