2023-05-17 17:38:511ST REVIEW FBC-2020 RES. GAS
 PERMIT- 23050475
 5/17/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P1 GAS RISER: LABEL ALL LENGTHS OF PIPING
 SHOWN AS EITHER PE, CSST, OR SCHEDULE 40 METALLIC AND
 PROVIDE THE SIZING TABLES USED FOR EACH- SEC. G2413.4
 FBC RES. IT IS NOT CLEAR WHERE THE UNDERGROUND PE
 TRANSITIONS TO CSST AND THE RISER SHOWS PIPING SLEEVED
 THROUGH FOOTINGS. PLEASE NOTE PE SHALL NOT BE INSTALLED
 UNDERNEATH BUILDINGS PER SEC. G2415.17.1 FBC RES.
  
 2) P1: THE FUTURE GENERATOR EXHAUST SHALL BE LOCATED A
 MINIMUM OF 10 FT. FROM ANY OPERABLE DOOR OR WINDOW
 OPENINGS, AND GRAVITY AND MECHANICAL AIR INTAKES
 INCLUDING VENTILATED SOFFITS- SEC. R303.5.1 FBC. PLEASE
 RELOCATE THE GENERATOR AND EXTEND THE PIPING IF
 NECESSARY TO MEET COMPLIANCE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  