Plan Review Notes
Plan Review Notes For Permit 23050467
Permit Number 23050467
Review Stop P
Sequence Number 1
Notes
Date Text
2023-05-19 12:13:331ST REVIEW FBC-2020 PLUMBING
 PERMIT- 23050467
 5/19/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS LS-1 & P100: PROVIDE PLUMBING FIXTURE
 CALCULATIONS FOR EACH BUILDING IN ACCORDANCE WITH TABLE
 403.1 FBC P. PROVIDE A SCHEDULE THAT SHOWS THE REQUIRED
 AND PROVIDED NUMBER OF FIXTURES. PLEASE NOTE MOP SINKS
 AND DRINKING FOUNTAINS ARE REQUIRED FOR BOTH BUILDINGS.
 BLDG. A IS MISSING THE DRINKING FOUNTAINS AND BLDG. B
 IS MISSING DRINKING FOUNTAINS AND MOP SINK. BLDG. A CAN
 CITE SEC. 410.4 AND PROVIDE DRINKING WATER IN A
 CONTAINER FREE OF CHARGE. IF CLAIMING THAT EXCEPTION
 PLEASE NOTE IT ON THE PLAN.
 A) CONCERNING THE DRINKING FOUNTAINS WHERE REQUIRED,
 TWO DRINKING SHALL BE PROVIDED- ONE FOR PERSONS IN
 WHEELCHAIRS, AND ONE FOR STANDING PERSONS- SEC. 410.3
 FBC P. PLEASE REVISE THE ARCHITECTURAL AND PLUMBING
 PLANS.
  
 2) S-1: AN ICE MACHINE IS SHOWN AT THE BAR HOWEVER THE
 PLUMBING PLANS DO NOT SHOW A WATER LINE OR DRAIN FOR
 THE APPLIANCE- SEC. 107.2.1 WPB.
  
 3) P100, P201, P400, & P500 GREASE INTERCEPTOR:
 COMMENTS A, B, & C BELOW SHALL ALSO APPLY TO THE
 SEPARATE GREASE INTERCEPTOR PERMIT- 22070156 WHICH IS
 STILL IN REVIEW.
 A) THE DRAINAGE FROM THE HAND SINK SHALL NOT DISCHARGE
 INTO THE GREASE WASTE INTERCEPTOR- SEC. 1003.3.1 FBC P.
 PLEASE ROUTE THE DRAINAGE TO SANITARY ALONG WITH
 DRAINAGE FROM THE ICE MACHINE- SEE COMMENT #2 ABOVE.
 B) PLEASE REMOVE THE HAND SINK FROM THE GREASE WASTE
 CALCULATIONS- SEC 1003.3.1.
 C) REFERENCE IS MADE TO A SAMPLING PORT DETAIL ON SHEET
 P0.1 WHICH IS NOT INCLUDED IN THE PLANS SETS. PLEASE
 NOTE THE CITY OF WPB UTILITIES DEPT. REQUIRES A TWO-WAY
 CLEANOUT ON THE INTERCEPTOR OUTLET PIPE TO BE USED AS A
 SAMPLING PORT.
  
 4) P500: AS A MEANS OF LIMITING THE HOT WATER
 TEMPERATURE AT THE WATER HEATER PLEASE PROVIDE AN ASSE
 1017 MASTER MIXING VALVE AT THE WATER HEATER- SEC.
 607.1.1 FBC P. PLEASE REVISE THE WATER HEATER DETAIL TO
 SHOW THE LOCATION OF THE DEVICE AND THE PIPING
 CONNECTIONS. IMPORTANT NOTE- SEC, 607.2.2 REQUIRES THE
 HWR LINE TO BE ROUTED TO THE COLD WATER INLET PIPE OF
 THE WATER HEATER AND THE COLD WATER INLET PIPE OR THE
 HOT WATER RETURN CONNECTION OF THE MIXING VALVE.
  
 5) S-1 & S-3: PLEASE SHOW THE CLEAR FLOOR SPACE
 DIAGRAMS AND DIMENSIONS FOR THE LAVATORIES TO VERIFY
 THE BATHROOM DOORS DO NOT SWING INTO THE SPACES- SEC.
 603.2.3 FBC ACC.
  
 6) S-3: PLEASE SHOW THE HEIGHTS OF THE GRAB BARS TO THE
 TOPS OF THE GRIPPING SURFACES- SEC. 609.4 FBC ACC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  