2023-06-26 14:01:14 | EMAILED LETTERS WERE NOT REVISED. SAME COMMENT APPLIES. |
| |
| RESIDENTIAL(R2) RE-ROOF BUILDING REVIEW COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| |
| 2- ROOF TO WALL CONNECTIONS: |
| THE BUILDING HAS A VALUATION OF MORE THAN $300,000. |
| NEED TO COMPLY WITH THE ROOF TO WALL CONNECTIONS AS |
| REQUIRED BY SEC. 706.8 FBC-EXISTING BUILDING. |
| STORM ROOFING, INC LETTER SUBMITTED IS NOT ACCEPTABLE. |
| THE ESTIMATE FOR THE ROOF TO WALL EVALUATION AND |
| INSTALLATION OF CONNECTIONS AT GABLE ENDS OR ALL |
| CORNERS HAS TO BE DONE BY LICENSED GENERAL OR BUILDING |
| CONTRACTOR NOT BY ROOFING CONTRACTOR. |
| ANOTHER OPTION IS TO SHOW THAT THE EXISTING ROOF TO |
| WALL CONNECTIONS MEET OR EXCEED FLORIDA BUILDING CODE. |
| |
| RESPONSE: |
| SITE PLAN AERIAL VIEW SUBMITTED SHOWS A THREE STORY |
| BUILDING. THERE ARE NOT TWO STORY APARTMENTS AT THE |
| ENDS OF THIS BUILDING. REVISE THE ROOF TO WALL |
| STRAPPING PROPOSAL AND THE ROOFING CONTRACTOR LETTER |
| DECLINING THE ROOF TO WALL CONNECTIONS WORK TO REFLECT |
| THE CORRECT NUMBER OF GABLE ENDS AND VALUE. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |