2023-06-07 15:03:00 | ADD OFFICE |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected] |
| CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| AMENDMENT |
| |
| CORRECTIONS NEEDED - |
| |
| 1) PLEASE SHOW THE ROOM USE ON THE DRAWINGS - FBC 107 |
| |
| 2) PLEASE SHOW THE ROOM DIMENSIONS - FBC 107 |
| |
| 3) PLEASE SHOW THE WALL HOURLY FIRE RATING FOR THE |
| OCCUPANCY CLASSIFICATION SEPARATION PER FBC TABLE 508.4 |
| |
| 4) PLEASE SHOW THE DOOR SIZES - FBC 107 |
| |
| 5) DRAWINGS DO NOT SHOW AS DIGITALLY SIGNED BY THE |
| ARCHITECT IN ADOBE READER - SIGNED AND SEALED DRAWINGS |
| IN PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY |
| SIGNED TO BE USED IN ELECTRONIC PLAN REVIEW. (A |
| CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED |
| A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF |
| E-SIGNATURE). |
| |
| 6) THIS IS NOT REQUIRED FOR PLAN REVIEW BUT JUST TO |
| INFORM YOU - A TEMPORARY/PARTIAL CERTIFICATE OF |
| OCCUPANCY WILL NEED TO BE APPLIED FOR BEFORE OCCUPANCY |
| SEE FBC WPB 111.3 TEMPORARY/PARTIAL OCCUPANCY. A |
| TEMPORARY/PARTIAL CERTIFICATE OF OCCUPANCY OR |
| CERTIFICATE OF COMPLETION MAY BE ISSUED FOR A PORTION |
| OR PORTIONS OF A BUILDING THAT MAY SAFELY BE OCCUPIED |
| PRIOR TO FINAL COMPLETION OF THE BUILDING. THE BUILDING |
| OFFICIAL MAY REQUIRE, ONCE ALL LIFE SAFETY ISSUES HAVE |
| BEEN COMPLIED WITH, AN APPLICANT TO PROVIDE ADEQUATE |
| CASH SURETY FOR UNFINISHED WORK OR REVISION OF PLANS |
| UNTIL A PERMANENT CERTIFICATE OF OCCUPANCY OR |
| CERTIFICATE OF COMPLETION IS GRANTED. |