Plan Review Notes
Plan Review Notes For Permit 23050347
Permit Number 23050347
Review Stop G
Sequence Number 1
Notes
Date Text
2023-06-20 09:14:441ST GAS REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMENDS 107.2.1 - PLEASE SUBMIT A FLOOR PLAN
 SHOWING THE LOCATION OF THE EXISTING WATER HEATER AND
 THE LOCATION OF THE NEW WATER HEATER. PLEASE SHOW THAT
 THE NEW WATER HEATER WILL BE 4 FEET FROM OPENINGS PER
 G2427.8 #2.
  
 2. 2017 WPB AMEND 107.3.5.3 (13) - PLEASE INCLUDE A
 RISER THAT SHOWS THE MODIFICATION TO THE GAS SYSTEM. BE
 SURE TO LABEL THE EXISTING AND NEW FOR CODE REVIEW. IT
 SHOULD BE NOTED THAT THIS PROPERTY CURRENTLY HAS AN
 APPLICATION IN FOR A GENERATOR THAT WILL HAVE BEARING
 ON THE GAS SYSTEM.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  