2023-05-09 13:50:22FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 (1) PANELS (?) SL-1 THROOUGH SL-7 FEED FROM ? PANEL
 SCHEDULES DO NOT REFLECT FEEDS.
  
 (2) MTS'S ARE FED BY A 50A PLUG? WHAT WOULD BE THE
 POWER FEEDER?
  
 (3) ATS AND SL-7 HOW ARE THEY FED FROM PANEL SS-3 50A?
 WHAT CIRCUIT NUMBER FEED THESE?
  
 (4) SS-1 THROUGH SS-3 PLEASE SUBMIT A LOAD CALCULATION
 AND PANEL SCHECULES.
  
 (5) NO ADD VALUE FOR THE ADDITIONAL WORK AND EQUIPMENT
 CUSTOMER OR CONTRACTOR SUPPLIED.