2023-05-31 14:07:09 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT- 23050314 |
| 5/31/2023 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET G-01: BASED ON WPB BUILDING DEPT. RECORDS |
| WHICH SHOW MULTIPLE EXPIRED PERMITS FOR PLUMBING UNDER |
| THE PREVIOUS OWNERSHIP, ALL PLUMBING WORK SHOWN ON THE |
| PLANS SHALL BE REVIEWED AS NEW INSTALLATIONS- SEC. |
| 107.2.1 WPB. THE CHANGE OF USE FROM HAIR SALON TO |
| RESTAURANT REQUIRES THE FOLLOWING PLANS AND DETAILS IN |
| ACCORDANCE WITH SECS. 1010.1, 1010.2, & 1010.3 FBC |
| EXISTING BUILDING AND THE FBC PLUMBING AND |
| ACCESSIBILITY CODES. |
| |
| A) PLUMBING FIXTURE CALCULATIONS IN ACCORDANCE WITH |
| TABLE 403.1 FBC P. PROVIDE A SCHEDULE THAT SHOWS THE |
| REQUIRED AND PROVIDED NUMBER OF FIXTURES. THE PLANS |
| APPEAR TO SHOW A RESTAURANT WHICH IS FOUND UNDER |
| ASSEMBLY CLASSIFICATION IN THE TABLE. THERE IS ONLY ONE |
| TOILET ROOM SHOWN HOWEVER SEPARATE FACILITIES FOR MALE |
| AND FEMALE USE ARE REQUIRED UNLESS MEETING ONE OF THE |
| FOUR EXCEPTIONS UNDER SEC. 403.2 FBC P. ALSO REQUIRED |
| ARE A SERVICE OR MOP SINK AND DRINKING FOUNTAIN. |
| DRINKING FOUNTAINS ARE NOT REQUIRED IF DRINKING WATER |
| IS PROVIDED TO PATRONS IN A CONTAINER FREE OF CHARGE- |
| SEE SEC. 410.4 FBC P. IF CHOOSING THIS OPTION PLACE A |
| NOTE UNDER THE FIXTURE CALCULATIONS. |
| |
| B) FBC ACCESSIBILITY COMPLIANCE- REFER TO SEC. 202.3, |
| 213.2, & 213.3 FBC ACC AND PROVIDE THE FOLLOWING |
| DRAWINGS AND DETAILS FOR THE NEW TOILET ROOM FIXTURES- |
| A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| WATER CLOSETS- SEC. 604.3. |
| B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| LAVATORIES- SEC. 606.2. |
| C) TURNING SPACE DIAMETERS- SEC. 304.3. |
| D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE |
| WALLS- SEC. 604.2. |
| E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED |
| FLOORS- SEC. 604.4. |
| F) HEIGHTS OF THE LAVATORY SINK RIM OR COUNTER SURFACE |
| FROM THE FINISHED FLOOR- SEC. 606.3. |
| G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO |
| THE REFLECTIVE SURFACES- SEC. 603.3 |
| H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| BARS FOR THE WATER CLOSETS- SEC. 604.5 & 609.4, FIGURES |
| 604. |
| I) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS ??? |
| SEC. 604.6. |
| J) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED |
| FROM THE FRONTS OF THE WATER CLOSETS- SEC. AND FIGURE |
| 604.7. |
| K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SEC. |
| 606.2. |
| |
| C) SANITARY DRAINAGE AND WATER RISER LAYOUT PLANS |
| INCLUDING RISER DRAWINGS FOR ALL NEW PLUMBING PIPING |
| INSTALLATIONS ASSOCIATE WITH THE NEW FIXTURE |
| INSTALLATIONS- SEC. 107.3.5.1.3 WPB. |
| |
| D) GREASE INTERCEPTOR PLANS- SEC. 1003.1 FBC P |
| INCLUDING THE FOLLOWING ITEMS- |
| A) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION |
| GUIDELINES WITH APPROVAL STAMP BY THE ENGINEER OF |
| RECORD- SECS.1003.3.5 OR 1003.3.7 FBC P. |
| B) EQUIPMENT SCHEDULE INDICATING THE MAKE AND MODEL AND |
| CAPACITY OF THE UNIT. |
| C) SIZING CALCULATIONS IN ACCORDANCE WITH ASME |
| A112.14.3, ASME A112.14.4, ASME A112.14.6, CSA B481.3, |
| OR PDI G101 FOR HYDROMECHANICAL TYPES; OR SEC. 1003.3.7 |
| FOR GRAVITY TYPES. |
| D) ENLARGED PIPING DIAGRAM INCLUDING LOCATIONS AND |
| SIZES OF INLETS, OUTLETS, VENTS AND CLEANOUTS. |
| E) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION |
| GUIDELINES WITH APPROVAL STAMP BY THE ENGINEER OF |
| RECORD- SECS.1003.3.5 OR 1003.3.7 FBC P. (PLEASE NOTE |
| THE SPECS MAY BE DEFERRED SUBMITTAL). |
| |
| PLEASE NOTE A SEPARATE PERMIT IS REQUIRED FOR THE |
| GREASE INTERCEPTOR. AT A MINIMUM, THE PERMIT |
| APPLICATION SHALL BE SUBMITTED PRIOR TO MAIN PLUMBING |
| PLAN APPROVAL. IF A CONTRACTORS IS NOT CURRENTLY |
| SELECTED FOR THE INSTALLATION, A PERMIT APPLICATION CAN |
| BE SUBMITTED TBD (TO BE DETERMINED). THE COMPLETED |
| APPLICATION SHALL BE EMAILED TO [email protected] |
| . YOU WILL THEN RECEIVE INSTRUCTIONS TO PAY FEES AND |
| UPLOAD PLANS. YOU MAY UPLOAD PLANS AND PAY FEES AT A |
| FUTURE DATE, BUT THE APPLICATION IS REQUIRED AT THIS |
| TIME. WE RECOMMEND THAT YOU PAY FEES AND UPLOAD PLANS |
| AT THE SAME TIME. AFTER YOU HAVE THE PERMIT(S) |
| GENERATED, NOTIFY ME VIA EMAIL AND I WILL CHANGE THE |
| REVIEW STATUS TO PASS. |
| |
| E) HOT WATER REQUIREMENTS- SEC. 607.1 FBC P INCLUDING- |
| A) LOCATION OF THE WATER HEATER. |
| B) EQUIPMENT SCHEDULE FOR THE WATER HEATER. |
| C) WATER HEATER PIPING DETAIL SHOWING THE LOCATION OF |
| ALL ASSOCIATED DEVICES INCLUDING THE THERMAL EXPANSION |
| CONTROL DEVICE, RECIRCULATION PUMP (IF INSTALLED), AND |
| REQUIRED TEMPERATURE LIMITING DEVICE PER SEC. 607.1.2. |
| |
| F) KITCHEN PLUMBING EQUIPMENT SCHEDULE AND LAYOUT PLAN. |
| PLEASE PROVIDE A NUMBERED OR LETTERED EQUIPMENT |
| SCHEDULE AND CORRESPONDING PLAN SHOWING MAKES AND |
| MODELS AND LOCATIONS OF THE 3-COMPARTMENT SINK, HAND |
| SINK, FLOOR SINKS AND FLOOR DRAINS, DISHWASHERS, |
| GLASSWASHERS, BEVERAGE DISPENSERS ETC.- SEC. 107.2.1 |
| WPB. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |