Plan Review Notes
Plan Review Notes For Permit 23050314
Permit Number 23050314
Review Stop P
Sequence Number 1
Notes
Date Text
2023-05-31 14:07:091ST REVIEW FBC-2020 PLUMBING
 PERMIT- 23050314
 5/31/2023
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET G-01: BASED ON WPB BUILDING DEPT. RECORDS
 WHICH SHOW MULTIPLE EXPIRED PERMITS FOR PLUMBING UNDER
 THE PREVIOUS OWNERSHIP, ALL PLUMBING WORK SHOWN ON THE
 PLANS SHALL BE REVIEWED AS NEW INSTALLATIONS- SEC.
 107.2.1 WPB. THE CHANGE OF USE FROM HAIR SALON TO
 RESTAURANT REQUIRES THE FOLLOWING PLANS AND DETAILS IN
 ACCORDANCE WITH SECS. 1010.1, 1010.2, & 1010.3 FBC
 EXISTING BUILDING AND THE FBC PLUMBING AND
 ACCESSIBILITY CODES.
  
 A) PLUMBING FIXTURE CALCULATIONS IN ACCORDANCE WITH
 TABLE 403.1 FBC P. PROVIDE A SCHEDULE THAT SHOWS THE
 REQUIRED AND PROVIDED NUMBER OF FIXTURES. THE PLANS
 APPEAR TO SHOW A RESTAURANT WHICH IS FOUND UNDER
 ASSEMBLY CLASSIFICATION IN THE TABLE. THERE IS ONLY ONE
 TOILET ROOM SHOWN HOWEVER SEPARATE FACILITIES FOR MALE
 AND FEMALE USE ARE REQUIRED UNLESS MEETING ONE OF THE
 FOUR EXCEPTIONS UNDER SEC. 403.2 FBC P. ALSO REQUIRED
 ARE A SERVICE OR MOP SINK AND DRINKING FOUNTAIN.
 DRINKING FOUNTAINS ARE NOT REQUIRED IF DRINKING WATER
 IS PROVIDED TO PATRONS IN A CONTAINER FREE OF CHARGE-
 SEE SEC. 410.4 FBC P. IF CHOOSING THIS OPTION PLACE A
 NOTE UNDER THE FIXTURE CALCULATIONS.
  
 B) FBC ACCESSIBILITY COMPLIANCE- REFER TO SEC. 202.3,
 213.2, & 213.3 FBC ACC AND PROVIDE THE FOLLOWING
 DRAWINGS AND DETAILS FOR THE NEW TOILET ROOM FIXTURES-
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSETS- SEC. 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORIES- SEC. 606.2.
 C) TURNING SPACE DIAMETERS- SEC. 304.3.
 D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE
 WALLS- SEC. 604.2.
 E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SEC. 604.4.
 F) HEIGHTS OF THE LAVATORY SINK RIM OR COUNTER SURFACE
 FROM THE FINISHED FLOOR- SEC. 606.3.
 G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SEC. 603.3
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SEC. 604.5 & 609.4, FIGURES
 604.
 I) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS ???
 SEC. 604.6.
 J) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SEC. AND FIGURE
 604.7.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SEC.
 606.2.
  
 C) SANITARY DRAINAGE AND WATER RISER LAYOUT PLANS
 INCLUDING RISER DRAWINGS FOR ALL NEW PLUMBING PIPING
 INSTALLATIONS ASSOCIATE WITH THE NEW FIXTURE
 INSTALLATIONS- SEC. 107.3.5.1.3 WPB.
  
 D) GREASE INTERCEPTOR PLANS- SEC. 1003.1 FBC P
 INCLUDING THE FOLLOWING ITEMS-
 A) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 GUIDELINES WITH APPROVAL STAMP BY THE ENGINEER OF
 RECORD- SECS.1003.3.5 OR 1003.3.7 FBC P.
 B) EQUIPMENT SCHEDULE INDICATING THE MAKE AND MODEL AND
 CAPACITY OF THE UNIT.
 C) SIZING CALCULATIONS IN ACCORDANCE WITH ASME
 A112.14.3, ASME A112.14.4, ASME A112.14.6, CSA B481.3,
 OR PDI G101 FOR HYDROMECHANICAL TYPES; OR SEC. 1003.3.7
 FOR GRAVITY TYPES.
 D) ENLARGED PIPING DIAGRAM INCLUDING LOCATIONS AND
 SIZES OF INLETS, OUTLETS, VENTS AND CLEANOUTS.
 E) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 GUIDELINES WITH APPROVAL STAMP BY THE ENGINEER OF
 RECORD- SECS.1003.3.5 OR 1003.3.7 FBC P. (PLEASE NOTE
 THE SPECS MAY BE DEFERRED SUBMITTAL).
  
 PLEASE NOTE A SEPARATE PERMIT IS REQUIRED FOR THE
 GREASE INTERCEPTOR. AT A MINIMUM, THE PERMIT
 APPLICATION SHALL BE SUBMITTED PRIOR TO MAIN PLUMBING
 PLAN APPROVAL. IF A CONTRACTORS IS NOT CURRENTLY
 SELECTED FOR THE INSTALLATION, A PERMIT APPLICATION CAN
 BE SUBMITTED TBD (TO BE DETERMINED). THE COMPLETED
 APPLICATION SHALL BE EMAILED TO [email protected]
 . YOU WILL THEN RECEIVE INSTRUCTIONS TO PAY FEES AND
 UPLOAD PLANS. YOU MAY UPLOAD PLANS AND PAY FEES AT A
 FUTURE DATE, BUT THE APPLICATION IS REQUIRED AT THIS
 TIME. WE RECOMMEND THAT YOU PAY FEES AND UPLOAD PLANS
 AT THE SAME TIME. AFTER YOU HAVE THE PERMIT(S)
 GENERATED, NOTIFY ME VIA EMAIL AND I WILL CHANGE THE
 REVIEW STATUS TO PASS.
  
 E) HOT WATER REQUIREMENTS- SEC. 607.1 FBC P INCLUDING-
 A) LOCATION OF THE WATER HEATER.
 B) EQUIPMENT SCHEDULE FOR THE WATER HEATER.
 C) WATER HEATER PIPING DETAIL SHOWING THE LOCATION OF
 ALL ASSOCIATED DEVICES INCLUDING THE THERMAL EXPANSION
 CONTROL DEVICE, RECIRCULATION PUMP (IF INSTALLED), AND
 REQUIRED TEMPERATURE LIMITING DEVICE PER SEC. 607.1.2.
  
 F) KITCHEN PLUMBING EQUIPMENT SCHEDULE AND LAYOUT PLAN.
 PLEASE PROVIDE A NUMBERED OR LETTERED EQUIPMENT
 SCHEDULE AND CORRESPONDING PLAN SHOWING MAKES AND
 MODELS AND LOCATIONS OF THE 3-COMPARTMENT SINK, HAND
 SINK, FLOOR SINKS AND FLOOR DRAINS, DISHWASHERS,
 GLASSWASHERS, BEVERAGE DISPENSERS ETC.- SEC. 107.2.1
 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  