Plan Review Notes For Permit 23050163 |
Permit Number |
23050163 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-05-19 11:36:54 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE IS AN INDICATION ON THE APPLICATION OF NEW | | WINDOWS, DOORS; HOWEVER, THERE ARE NO FLOOR/BUILDING | | PLAN SHEETS SHOWING THE LOCATIONS OF THE PROPOSED | | CHANGES. | | | | PER NFPA 1 | | | | 1.7.12 PLANS AND SPECIFICATIONS. | | | | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE | | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH | | APPLICABLE CODES AND STANDARDS | | | | | | FOR THE OFFICIAL RECORD, PLEASE PROVIDE A BUILDING | | FLOOR PLAN SHOWING THE LOCATIONS OF THE WINDOWS AND | | DOORS, INTERIOR & EXTERIOR IF APPLICABLE. | | | | ENSURE A DOOR SCHEDULE IS PROVIDED FOR THE ENTRY DOORS | | WITH HARDWARE LOCKS & LATCHES IN COMPLIANCE WITH NFPA | | 101 CH 7, MEANS OF EGRESS. | | | | | | | | 2) THERE IS AN INDICATION ON THE APPLICATION OF A/C, | | ELECTRIC PANELS; HOWEVER, THERE ARE NO ELECTRICAL PLAN | | NOR PRODUCT SPEC SHEETS | | | | FOR THE OFFICIAL RECORD, PLEASE PROVIDE AN ELECTRICAL | | PLAN SHEET IN COMPLIANCE WITH NFPA 70 | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|