2023-05-12 11:55:24 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| 1) THERE IS AN INDICATION OF A GLUE DOWN WOOD FLOOR, |
| BUT NO SPEC SHEET NOR A PRODUCT NAME FOR THE ACTUAL |
| PROPOSED WOOD FLOORING NOR THE PROPOSED GLUE PRODUCT. |
| |
| WOOD FLOORING AND GLUE PRODUCTS ARE MANUFACTURED AROUND |
| THE WORLD BUT NOT ALL ARE TESTED AND MEETING LISTED AND |
| NFPA STANDARDS. |
| |
| PER NFPA 101, CH 30 |
| |
| 30.3.3.3 INTERIOR FLOOR FINISH. |
| 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN |
| ACCORDANCE WITH |
| SECTION 10.2. |
| |
| 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH |
| 10.2.2.2 |
| ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL |
| HAVE A |
| MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. |
| |
| FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE PEROPSED |
| WOOD FLOORING NAME AND THE PRODUCT SPEC SHEETS |
| INDICATING THE FIRE BEHAVIOR RATING. |
| |
| IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE, |
| NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC SHEETS |
| WOULD NOT BE REQUIRED. |
| |
| PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL |
| FLOORING, WOOD/VINYL LAMINATES, ETC. |
| |
| |
| |
| 2) THERE IS AN INDICATION OF WORK ON A FIRE RATED |
| CORRIDOR WALL IN BATHROOM. |
| |
| ENSURE FIRE RATED TENANT/CORRIDOR SEPARATION WALLS |
| ARE MAINTAINED & REPAIRED IF DAMAGED. |
| |
| PROVIDE A NOTE OF ACKNOWLEDGMENT OF THE PROPOSED FLOOR |
| PLAN. |
| |
| |
| 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| PROTECT FIRE SPRINKLERS AND FIRE ALARM DEVICES AND |
| EQUIPMENT. |
| DO NOT PAINT OVER SPRINKLER HEADS AND/OR FIRE ALARM |
| DEVICES/EQUIPMENT. |
| THE FS AND FA SYSTEMS SHALL BE MAINTAINED THROUGHOUT |
| DEMO AND CONSTRUCTION. |
| PLEASE ENSURE THE APPLICABLE PROTECTION AND PROVIDE A |
| NOTE OF ACKNOWLEDGMENT ON THE FLOOR PLAN. |
| |