Plan Review Notes
Plan Review Notes For Permit 23050062
Permit Number 23050062
Review Stop M
Sequence Number 1
Notes
Date Text
2023-05-25 13:32:23PLAN DENIED
 1) REFER TO SECTION M1502.4.1 MATERIAL AND SIZE. WALL
 WITH
 CLOTHES DRYER EXHAUST DUCT MUST BE AT LEAST 2X6 FBC
 RESIDENTIAL CODE 2020.
 2) PLEASE PROVIDE INSTALLATION INSTRUCTIONS FOR KITCHEN
 HOOD
 PER SECTION M1503.4 MAKE UP AIR REQUIRED 2020 FBC
 RESIDENTIAL CODE
 3) ENERGY CALCULATIONS AND PLAN DO NOT MATCH SEER AND
 LOCATION OF
 AIR HANDLERS ON EQUIPMENT SCHEDULE ON THE PLANS.