2023-06-21 14:12:43 | ELECTRIC REVIEW FAILED |
| |
| 1) PLEASE DETAIL ALL TREATMENT ROOM RECEPTACLES TO |
| COMPLY WITH THE FOLLOWING: |
| 517.13 GROUNDING OF RECEPTACLES AND FIXED ELECTRICAL |
| EQUIPMENT IN PATIENT CARE SPACES |
| (A) WIRING METHODS. ALL BRANCH CIRCUITS SERVING PATIENT |
| CARE SPACES SHALL BE PROVIDED WITH AN EFFECTIVE |
| GROUND-FAULT CURRENT PATH BY INSTALLATION IN A METAL |
| RACEWAY SYSTEM OR A CABLE HAVING A METALLIC ARMOR OR |
| SHEATH ASSEMBLY |
| |
| 2) PLEASE DETAIL ANY RECEPTACLES WITHIN 6 FEET OF ANY |
| SINK AS BEING GFI PROTECTED IN ACCORDANCE WITH NEC |
| 210.8 (B)(5). THIS SHOULD INCLUDE RECEPTACLES WITHIN 6 |
| FEET OF TREATMENT ROOM SINKS |
| |
| 3) PLEASE DETAIL ANY APPLICABLE RECEPTACLES ARE TAMPER |
| RESISTANT IN ACCORDANCE WITH NEC 406.12 |
| |
| 4) PLEASE PROVIDE A NOTE STATING ALL LOW VOLTAGE WIRING |
| INCLUDING BUT NOT LIMITED TO VOICE, DATA, FIRE ALARM, |
| ACCESS CONTROL, SECURITY AND SIGNS REQUIRE A SEPARATE |
| PERMIT |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. |
| |
| CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2020 7TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| 7TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| V/R, |
| |
| MICHAEL PETERSON |
| ELECTRICAL PLANS EXAMINER |
| [email protected] |
| 561-805-6746 |
| |
| |