2023-06-30 11:01:24PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10
 FEET FROM ANY OPENINGS INTO A BUILDING. R303.5.1 INTAKE
 OPENINGS.MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE
 OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET (3048
 MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS
 VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS,
 PARKING LOTS AND LOADING DOCKS.
 OPENINGS LESS THAN 5 FEET FROM THE GENERATOR EXHAUST
 ARE NOT ALLOWED. FOR OPENINGS THAT ARE BETWEEN 5 FEET
 TO 10 FEET FROM THE PROPOSED GENERATOR EXHAUST
 LOCATION, STATE ON THE PLANS THAT A CO DETECTOR WILL BE
 INSTALLED INSIDE THE BUILDING, EITHER ON THE CEILING OR
 5 FEET ABOVE THE FLOOR, NEXT TO EACH OPENING THAT IS
 BETWEEN 5 FEET TO 10 FEET FROM THE PROPOSED GENERATOR
 EXHAUST LOCATION.