Plan Review Notes For Permit 23041466 |
Permit Number |
23041466 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2023-06-30 11:01:24 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10 | | FEET FROM ANY OPENINGS INTO A BUILDING. R303.5.1 INTAKE | | OPENINGS.MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE | | OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 | | MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS | | VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, | | PARKING LOTS AND LOADING DOCKS. | | OPENINGS LESS THAN 5 FEET FROM THE GENERATOR EXHAUST | | ARE NOT ALLOWED. FOR OPENINGS THAT ARE BETWEEN 5 FEET | | TO 10 FEET FROM THE PROPOSED GENERATOR EXHAUST | | LOCATION, STATE ON THE PLANS THAT A CO DETECTOR WILL BE | | INSTALLED INSIDE THE BUILDING, EITHER ON THE CEILING OR | | 5 FEET ABOVE THE FLOOR, NEXT TO EACH OPENING THAT IS | | BETWEEN 5 FEET TO 10 FEET FROM THE PROPOSED GENERATOR | | EXHAUST LOCATION. |
|