2023-05-31 13:54:16 | RESIDENTIAL(R3) RE-ROOF SECOND BUILDING REVIEW COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #23041431 |
| 2737 S FLAGLER DR |
| |
| 1- FLAT ROOF FLORIDA PRODUCT APPROVAL: |
| ORIGINAL COMMENT: |
| A)CLEARLY MARK WHICH APPROVED ASSEMBLY IS GOING TO BE |
| INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN |
| PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. |
| NOTE: PLEASE UPLOAD THE FLORIDA PRODUCT APPROVAL COVER |
| PAGE AND INSTALLATION INSTRUCTIONS ON THE SAME PDF. |
| |
| RESPONSE: |
| INFORMATION UPLOADED TO PROJECTDOX ON 05/26/23 IS |
| MISMATCHING TWO DIFFERENT PRODUCT APPROVALS. CONTRACTOR |
| UPLOADED THE REVISED PRODUCT APPROVAL COVER PAGE |
| FL2533-R29 BUT THE INSTALLATION INSTRUCTIONS SUBMITTED |
| ARE FOR THE OLD REVISION FL2533-R28. SELECTED SYSTEM |
| W-67 IS NOT THE SAME FOR FL2533-R28 AND FL2533-R289. |
| NEED TO SUBMIT MATCHING FLORIDA PRODUCT APPROVAL COVER |
| PAGE AND INSTALLATION INSTRUCTIONS TO AVOID |
| CONFLICTS/DELAYS. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| ORIGINAL COMMENT: |
| B)BASED ON OLD FLORIDA PRODUCT APPROVAL FL2533-R28 |
| SUBMITTED, IT LOOKS LIKE THE PROPOSED ASSEMBLY IS W-68. |
| NEED TO PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS |
| AS REQUIRED BY LIMITATION #5.7.2 OF PRODUCT APPROVAL |
| SUBMITTED. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| RESPONSE: |
| COORDINATE WITH ITEM ABOVE. MISMATCHING TWO DIFFERENT |
| PRODUCT APPROVALS. |
| |
| ORIGINAL COMMENT: |
| 2- HIP AND RIDGE TILE INSTALLATION. PROVIDE COMPLETE |
| DETAILS AND SPECIFICATIONS FOR HIP AND RIDGE |
| INSTALLATION AS REQUIRED BY SEC. R905.3.7.1 |
| FBC-RESIDENTIAL. PROVIDE SPECIFICATIONS IN ACCORDANCE |
| WITH FRSA/TRI FLORIDA HIGH WIND CONCRETE AND CLAY TILE |
| INSTALLATION MANUAL (6TH EDITION) OR THE |
| RECOMMENDATIONS OF RAS 118, 119 OR 120. |
| ALTERNATIVE: IF USING METAL SUPPORT, THEN PROVIDE |
| PRODUCT APPROVAL FOR HIP AND RIDGE METAL SUPPORT AND |
| CLEARLY MARK ATTACHMENT METHOD. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| NEW COMMENTS BASED ON INFORAMTION SUBMITTED: |
| 3- ENGINEER TO REVISE THE ROOF COVERINGS ATTACHMENT |
| CALCULATIONS SUBMITTED: |
| A) COORDINATE SELECTED ASSEMBLY WITH CURRENT REVISED |
| PRODUCT APPROVAL FL2533-R29. SEE ITEM #1(A) ABOVE. |
| |
| B)ENGINEER TO PROVIDE SKETCH SHOWING HOW THE PROPOSED |
| NAILS ARE GOING TO BE INSTALLED FOR THE SEVEN CENTER |
| ROWS IN ZONE 3. NEED TO VERIFY THAT FASTENER SEPARATION |
| IS NOT LESS THAN 4"O.C. AS REQUIRED BY SEC. 8.1 OF RAS |
| 117. |
| SEC. 107.2.1.2 CITY AMENDMENTS. |
| |
| C)ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE |
| REQUIREMENTS OF FBPE. NEED A SEPARATE TEXT BOX WITH THE |
| TEXT BOX LANGUAGE IDENTICAL TO THE SAMPLES SHOWN BY |
| FBPE. |
| SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU |
| MENTS/??? AND REVISE DIGITAL SIGNATURE AS REQUIRED. |
| |
| 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND |
| SEALING ELECTRONICALLY TRANSMITTED PLANS, |
| SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |
| [email protected] |
| |