Plan Review Notes For Permit 23041431 |
Permit Number |
23041431 |
|
Review Stop |
SIGNATURE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-05-31 13:55:53 | SIGNATURE REVIEW: | | | | 1- ENGINEER TO REVISE THE ROOF COVERINGS ATTACHMENT | | CALCULATIONS SUBMITTED: | | A) COORDINATE SELECTED ASSEMBLY WITH CURRENT REVISED | | PRODUCT APPROVAL FL2533-R29. SEE ITEM #1(A) ABOVE. | | | | B)ENGINEER TO PROVIDE SKETCH SHOWING HOW THE PROPOSED | | NAILS ARE GOING TO BE INSTALLED FOR THE SEVEN CENTER | | ROWS IN ZONE 3. NEED TO VERIFY THAT FASTENER SEPARATION | | IS NOT LESS THAN 4"O.C. AS REQUIRED BY SEC. 8.1 OF RAS | | 117. | | SEC. 107.2.1.2 CITY AMENDMENTS. | | | | C)ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE | | REQUIREMENTS OF FBPE. NEED A SEPARATE TEXT BOX WITH THE | | TEXT BOX LANGUAGE IDENTICAL TO THE SAMPLES SHOWN BY | | FBPE. | | SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU | | MENTS/??? AND REVISE DIGITAL SIGNATURE AS REQUIRED. | | | | 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND | | SEALING ELECTRONICALLY TRANSMITTED PLANS, | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
|