Plan Review Notes
Plan Review Notes For Permit 23041354
Permit Number 23041354
Review Stop B
Sequence Number 2
Notes
Date Text
2023-05-19 18:42:20RESIDENTIAL(R3) RE-ROOF BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #23041354
 1422 6TH ST
  
 NOTE:
 LEVEL 1 ALTERATION. SEC. 602 FBC-EXISTING BUILDING.
 SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK SHALL
 COMPLY WITH THE MATERIALS AND METHODS REQUIREMENTS IN
 THE FLORIDA BUILDING CODE.
  
 1- ENGINEER DOING THE ROOF COVERINGS ATTACHMENT
 CALCULATIONS IS STATING THAT "ZONE 1' AND 1 ARE LIKELY
 NOT APPLICABLE DUE TO ROOF SIZE AND GEOMETRY". THE ROOF
 ZONES NEED TO BE CLEARLY IDENTIFIED. ENGINEER TO
 PROVIDE SKETCH SHOWING THE ROOF ZONES APPLICABLE TO
 THIS PROJECT.
 SEC. 107.2.1.2 CITY AMENDMENTS.
  
 2- ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE
 REQUIREMENTS OF FBPE. NEED A SEPARATE TEXT BOX WITH THE
 TEXT BOX LANGUAGE IDENTICAL TO THE SAMPLES SHOWN BY
 FBPE.
 SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU
 MENTS/... AND REVISE DIGITAL SIGNATURE AS REQUIRED.
  
 SEC. 61G15-23.004 F.A.C. . PROCEDURES FOR DIGITALLY
 SIGNING AND SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,