2023-05-04 14:55:14 | PERMIT- 23041346 |
| 5.4.2023 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| FHDA- FAIR HOUSING DESIGN ACT MANUAL |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1. FAIR HOUSING ACT COMPLIANCE:1701 SOUTH FLAGLER DRIVE |
| CONDOMINIUMS ARE SUBJECT TO COMPLIANCE WITH FAIR |
| HOUSING ACCESSIBILITY GUIDELINES WHICH CAME INTO EFFECT |
| FOR MULTIFAMILY HOUSING BUILT FOR FIRST OCCUPANCY AFTER |
| MARCH 13, 1991. THE SUBMITTED PLAN SHOWING A BATHTUB TO |
| SHOWER MUST BE MODIFIED IN ACCORDANCE WITH COMMENTS #2 |
| & #3 BELOW. |
| |
| PLEASE NOTE: AS AN ALTERNATIVE TO MEETING THE |
| GUIDELINES FOR THE BATH ALTERATIONS, THE OWNER AND |
| DESIGNER OF RECORD FOR THE PROPOSED PROJECT MAY PROVIDE |
| A SIGNED AND NOTARIZED AFFIDAVIT WHICH WOULD INDICATE |
| ACKNOWLEDGEMENT THAT THE PROPOSED DESIGN DOES NOT MEET |
| THE REQUIREMENTS OF THE FAIR HOUSING ACCESSIBILITY |
| GUIDELINES, BUT WILL ALSO REQUIRE THE OWNER TO AGREE TO |
| REVERT THE UNIT BACK TO COMPLIANCE AT TIME OF SALE IF |
| REQUESTED BY THE BUYER. IF THIS OPTION IS CHOSEN, |
| PLEASE SEND AN EMAIL TO [email protected] AND I WILL SEND A |
| COPY OF THE FAIR HOUSING AFFIDAVIT. ONE OF THE BATHROOM |
| MUST MEET FAH GUIDELINE. |
| |
| 2. REFER TO PAGES 7.56- 7.59 OF THE FHDA MANUAL AND |
| PROVIDE A DRAWING FOR THE BATHROOM THAT SHOWS THE |
| DIMENSIONS OF THE SHOWER AND THE REQUIRED 30X48-INCH |
| CLEAR FLOOR SPACE DIAGRAM POSITIONED PARALLEL TO THE |
| SHOWER AND FLUSH WITH THE CONTROL WALL. PLEASE NOTE IF |
| THE SHOWER IS THE ONLY BATHING FIXTURE IN THE CONDO IT |
| SHALL BE MINIMUM 36X36-INCHES IN SIZE. IT IS ALSO |
| REQUIRED THAT NO OTHER FIXTURES SHALL OBSTRUCT THE |
| CLEAR FLOOR SPACE REQUIRED FOR THE SHOWER WITH THE |
| EXCEPTION OF A LAVATORY WHICH MAY OVERLAP BY 6-INCHES. |
| THE LAVATORY SHALL BE A WALL HUNG WITH KNEE AND TOE |
| CLEARANCES OR HAVE A REMOVABLE CABINET. |
| |
| 3. PROVIDE AN ELEVATION DETAIL FOR THE SHOWER THAT |
| SHOWS THE LOCATIONS OF REQUIRED GRAB BAR REINFORCEMENTS |
| IN ACCORDANCE WITH PAGE 6.13. OR NOTE ON THE PLAN THAT |
| THE REINFORCEMENT WILL BE PROVIDED. |
| |
| 4. CLARIFY IF THE EXISTING TUB DRAIN WILL BE RE-USED OR |
| IF A NEW DRAIN WILL BE INSTALLED IN THE CENTER OF THE |
| SHOWER. PLEASE NOTE THE FOLLOWING FOR NEW DRAIN |
| INSTALLATIONS: |
| RELOCATING THE SHOWER DRAIN OUTLET MAY REQUIRE THE |
| FLOOR TO BE X-RAYED TO IN ORDER TO LOCATE REINFORCING |
| STEEL OR POST STRESSED FLOOR TENDONS. PLEASE PLACE A |
| NOTE ON THE PLANS TO VERIFY COMPLIANCE WILL BE MET- |
| SECTION 107.2.1 WPB. |
| NEW DRAINPIPE PENETRATIONS OF THE EXISTING SLAB WILL |
| REQUIRE FIRESTOPPING TO SEAL THE ANNULAR SPACE AROUND |
| THE PIPING. PROVIDE A UL TESTED AND APPROVED |
| FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN- SECTION 315.1 |
| FBC P AND SECTION 714.4.1.2 FBC B. |
| |
| 5. [FBC 1207.3]STRUCTURE-BORNE SOUND. FLOOR/CEILING |
| ASSEMBLIES |
| BETWEEN DWELLING UNITS AND SLEEPING UNITS OR BETWEEN A |
| DWELLING |
| UNIT OR SLEEPING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN |
| THE STRUCTURE SHALL HAVE AN IMPACT INSULATION CLASS |
| RATING OF |
| NOT LESS THAN 50, OR NOT LESS THAN 45 IF FIELD TESTED, |
| WHEN TESTED |
| IN ACCORDANCE WITH ASTM E492. |
| |
| 6. [FBC 603.1]ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| OR UL 723. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| |
| |