2023-04-27 09:29:29 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| PHONE (561) 805-6656 |
| EMAIL: [email protected] |
| |
| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| |
| 1. FBC B 107.1 IF THE DESIGN PROFESSIONAL IS AN |
| ARCHITECT, INTERIOR DESIGNER, OR ENGINEER LEGALLY |
| REGISTERED UNDER THE LAWS OF THE STATE OF FLORIDA |
| REGULATING THE PRACTICE OF ARCHITECTURE OR INTERIOR |
| DESIGN AS PROVIDED FOR IN CHAPTER 481, FLORIDA |
| STATUTES, PART I, OR LANDSCAPE ARCHITECTURE AS PROVIDED |
| FOR IN CHAPTER 481, FLORIDA STATUTES, PART II, OR |
| ENGINEERING AS PROVIDED FOR IN CHAPTER 471, FLORIDA |
| STATUTES, THEN HE OR SHE SHALL AFFIX HIS OR HER |
| OFFICIAL SEAL TO SAID DRAWINGS, SPECIFICATIONS AND |
| ACCOMPANYING DATA, AS REQUIRED BY FLORIDA STATUTE. |
| ENGINEER???S LETTER NOT PROPERLY SEALED. |
| 2. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL16730-R41 |
| IS NOT APPROVED FOR USE OUTSIDE HVHZ. CITY OF WEST PALM |
| BEACH IS NOT LOCATED IN A HVHZ. PROVIDE A COMPLETE SET |
| OF 2020 CODE VERSION PRODUCT APPROVALS/NOA'S FOR THE |
| PROPOSED FLAT ROOF SYSTEM TO BE USED. INCLUDE COVER |
| PAGE, EVALUATION REPORTS AND INSTALLATION INSTRUCTIONS |
| FOR SYSTEM USED. ALL APPLICABLE DETAILS AND ATTACHMENTS |
| MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL |
| DRAWINGS. DETAILS AND ATTACHMENTS NOT SPECIFICALLY |
| COVERED IN PRODUCT APPROVALS WILL NEED SITE-SPECIFIC |
| ENGINEERING. |
| 3. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL5259-R34 |
| HAS BEEN REVISED TO FL5259-R38. PLEASE PROVIDE A |
| COMPLETE SET TO INCLUDE COVER PAGE(S); IT COVERS |
| MULTIPLE PRODUCT TYPES; ROOF COVER OPTIONS; ALLOWABLE |
| UNDERLAYMENT/TILE-ADHESIVE COMBINATIONS, ALLOWABLE |
| SUBSTRATES & ATTACHMENT LIMITATIONS. SELECT OPTIONS |
| FROM EACH CATEGORY TO BE USED; SELECT FROM TABLE 4A |
| DIRECT-TO-DECK UNDERLAYMENT IN TILE ROOF APPLICATIONS |
| OR TABLE 4B 2-PLY UNDERLAYMENT SYSTEMS IN TILE ROOF |
| APPLICATIONS. ALL APPLICABLE DETAILS AND ATTACHMENTS |
| MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL |
| DRAWINGS. |
| 4. FBC B 107.3.4.1. SUBMIT ALL PRODUCT |
| APPROVALS/NOA???S THAT SHALL BE USED FOR THIS ROOFING |
| PROJECT TO THE REGISTERED DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| OFFICIAL. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST |
| BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. |
| NOTE: MUST BE SIGNED BY ARCHITECT/ENGINEER BEFORE |
| SUBMITTING. REVIEW STAMP WITH INITIALS. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |