Plan Review Notes For Permit 23041305 |
Permit Number |
23041305 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-05-03 12:39:50 | 1ST REVIEW FBC-2020 FUEL GAS | | PERMIT- 23041305 | | 5/3/23 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) INDICATE HOW COMBUSTION AIR WILL BE PROVIDED TO THE | | NEW WATER HEATER AND RANGE- SEC. G2407.1 FBC RES. IF | | USING THE STANDARD METHOD OF INDOOR AIR THE REQUIRED | | VOLUME SHALL BE 50 CU.FT. PER 1000 BTUH OF THE INPUT | | RATINGS- SEC. G2407.5.1 FBC RES. PLEASE REVISE THE | | LOCATION PLAN TO SHOW THE ACTUAL ROOMS THE APPLIANCES | | WILL BE LOCATED IN WITH ROOM DIMENSIONS. | | | | 2) PROVIDE A VENTING DIAGRAM FOR THE NEW WATER HEATER. | | SHOW THE TYPE AND SIZE OF VENT, VENT RUN, AND | | TERMINATION LOCATION- SEC. & TABLE G2427.4 FBC RES. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | | | |
|