2023-05-24 09:15:47 | WEST PALM BEACH DEVELOPMENT SERVICES |
| BUILDING DIVISION |
| 2020 FBC- BUILDING PLAN REVIEW |
| W.P.B. SUBMITTAL: 23041300 |
| W. P. B. PERMIT: 22101425 / 22101430 |
| ADD: 550 EXECUTIVE CENTER DR. |
| CONT: LEGACY CONSTRUCTION |
| TEL: 218-297-2170 |
| E-MAIL: [email protected] |
| |
| 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. MAY 24, 2023 |
| ACTION: DENIED |
| |
| 1A) THIS SUBMITTAL WAS BROUGHT IN FOR ONE BUILDING ONLY |
| NOT SHOWN ON THE SUBMITTAL SHEET PERMIT 23041300!!!!! |
| |
| 1B) LEGACY CONSTRUCTION SUBMITTAL #8.3-1.0 WINDOWS AND |
| PATIO DOORS & 8.3- WINDOWS. COVER SHEET STATES SPEC |
| SECTION IS 8.3 WINDOWS 12-20-2022 WHERE IS THE SECTION |
| 8.3-1.0? ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 2) NOT INCLUDE IN THIS SUBMITTAL IS SHEET A-900 WINDOW |
| AND DOORS WITH WIND DESIGN CRITERIA AND ASSOCIATED |
| PRESSURES. 2020 WEST PALM BEACH AMENDMENTS TO THE |
| FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION |
| 107.2.1. CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT |
| CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| BY THE BUILDING OFFICIAL. |
| |
| 3)MISSING NOT COMPLETED IN ANY OF THE PRODUCT |
| APPROVALS. IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY |
| IN THE PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER |
| OF RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| IDENTIFY THE OPENING WIDTH & HEIGHT, SILL HEIGTH, TYPE |
| OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED OR |
| REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND |
| ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2020 FBC-B |
| 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE |
| INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER???S |
| INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| |
| 4) MISSING IN THE SLIDING GLASS NOA 22-1205.01 IS AS |
| STATED ABOVE THE SILL HEIGHT FOR THE SLIDING GLASS |
| DOORS IN ACCORDANCE WITH 2020 FBC-B HABITAL SPACES/ |
| 1709.5.1.1FBC-B EXTERIOR WINDOWS AND DOORS. (EXCEPTION) |
| 2. DOOR ASSEMBLIES INSTALLED WHERE THE OVERHANG (OH) |
| RATIO IS EQUAL TO OR MORE THAN 1 NEED NOT BE TESTED FOR |
| WATER INFILTRATION. THE OVERHANG RATIO SHALL BE |
| CALCULATED BY THE FOLLOWING EQUATION: |
| OH RATIO = OH LENGTH/OH HEIGHT |
| WHERE: |
| OH LENGTH = THE HORIZONTAL MEASURE OF HOW FAR AN |
| OVERHANG OVER A DOOR PROJECTS OUT FROM DOOR SURFACE. |
| OH HEIGHT = THE VERTICAL MEASURE OF THE DISTANCE FROM |
| THE DOOR SILL TO THE BOTTOM OF THE OVERHANG OVER A |
| DOOR. |
| |
| TECHNICAL SHEET 7 OF 21 FIGURE 1 PROVIDES THE EXAMPLE |
| OF OVERHANG LENGTH VERSES WALL HEIGHT. TABLE 1 POSITIVE |
| PRESSURES THE MINIMUM SILL HEIGHT REQUIRED WOULD BE 3 |
| ?? INCHES GOOD FOR +60.0 PSF, THE 2 ?? INCH SILL HEIGHT |
| IS GOOD FOR + 38.7 NOT MEETING THE REQUIRED + 47.1 PSF. |
| |
| 5) A TRANSMITTAL LETTER / NARRATIVE LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| REVIEW, SUBSEQUENT |
| REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE. |
| |
| MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| PART-TIME/ SEMI-RETIRED. |
| |
| IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| BACK INTO THE OFFICE CALL |
| (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| THANK YOU. |
| |
| JAMES A. WITMER BN, PX, SFP, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |