2023-07-03 11:19:15 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT- 23041277 |
| 7/3/2023 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET P201 & P301: PLEASE NOTE THE GREASE |
| INTERCEPTOR SHALL RECEIVE WASTE ONLY FROM FIXTURES AND |
| EQUIPMENT THAT ALLOW FATS, OILS, AND GREASE TO BE |
| DISCHARGED- SEC. 1003.3.1 FBC P. THE PLANS APPEAR TO |
| SHOW DRAINAGE FROM HAND SINKS (P14688) AND FLOOR SINKS |
| BELOW ICE BINS DRAINING INTO THE GREASE WASTE LINE |
| WHICH IS NOT ALLOWED. |
| |
| 2) P201 & P301: ITEMS 15186 & 19742 SHOWN ON THE PLANS |
| ARE NOT SHOWN IN THE SCHEDULE- SEC. 107.2.1 WPB & |
| 1003.3.1 FBC P. IT APPEARS THE 3-COMPARTMENT SINK IS |
| NOT IDENTIFIED. |
| |
| 3) P402: PLEASE PROVIDE GREASE WASTE CALCULATIONS IN |
| ACCORDANCE WITH SEC. 1003.3.5 FBC P. |
| |
| 4) A SEPARATE PERMIT IS REQUIRED FOR INSTALLATION OF |
| THE GREASE INTERCEPTOR HOWEVER THE PERMIT APPLICATION |
| IS REQUIRED TO BE SUBMITTED PRIOR TO THE MAIN PLUMBING |
| PLAN APPROVAL. YOU CAN SUBMIT AN APPLICATION ???TBD??? |
| (TO BE DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR |
| SELECTED BY EMAILING A COMPLETED PERMIT APPLICATION TO |
| [email protected] . YOU WILL RECEIVE INSTRUCTIONS |
| TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND |
| PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS |
| REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES |
| AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE |
| PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL AND I WILL |
| CHANGE THE REVIEW STATUS TO PASS. |
| |
| 5) P202 & P301: SHOW THE LOCATIONS OF REQUIRED INLINE |
| BACKFLOW PREVENTERS FOR WATER SUPPLY LINES TO COFFEE |
| AND EXPRESSO MACHINES, ICE MAKERS, FILTER SYSTEMS ETC- |
| SEC. 608.3 FBC P. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |