Plan Review Notes
Plan Review Notes For Permit 23041277
Permit Number 23041277
Review Stop E
Sequence Number 1
Notes
Date Text
2023-07-05 13:25:45ELECTRIC REVIEW FAILED
  
 1) ROOMS LABELED WORKROOM A, B AND BACK BAR APPEAR TO
 BE CLASSIFIED AS A KITCHEN IN ACCORDANCE WITH NEC 100
 DEFINITIONS. EQUIPMENT DETAILED ON KITCHEN EQUIPMENT
 SCHEDULE DETAIL THEY ARE TO TERMINATE TO RECEPTACLES
 WHICH ARE REQUIRED TO BE GFIC PROTECTED IN ACCORDANCE
 WITH NEC 210.8. PLEASE CORRECT PLANS TO INDICATE ALL
 RECEPTACLES LOCATED IN THESE KITCHEN AREAS COMPLY WITH
 NEC 210.8
  
 NEC 210.8 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION
 FOR PERSONNEL
 (B) OTHER THAN DWELLING UNITS.
 ALL SINGLE-PHASE RECEPTACLES RATED 150 VOLTS TO GROUND
 OR LESS, 50 AMPERES OR LESS AND THREE-PHASE RECEPTACLES
 RATED 150 VOLTS TO GROUND OR LESS, 100 AMPERES OR LESS
 INSTALLED IN THE FOLLOWING LOCATIONS SHALL HAVE
 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR
 PERSONNEL.
 (2) KITCHENS
  
 NEC 100 DEFINITIONS
 KITCHEN.
 AN AREA WITH A SINK AND PERMANENT PROVISIONS FOR FOOD
 PREPARATION AND COOKING
  
 3) SHEET E202 REFERS, INCORRECTLY TO A DETAIL ON SHEET
 E 301 DETAIL 7 THAT APPEARS TO BE SHOWN ON SHEET E 302
 DETAIL 7. PLEASE CORRECT AS APPLICABLE. FBC 107.2
  
 4) SHEET E 303 DETAIL 2, BANQUET CLOSTER INDICATES A
 DIMMED DUPLEX RECEPTACLE. NEC 404.14 STATES GENERAL USE
 DIMMER SWITCHES SHALL ONLY BE USED TO CONTROL PERMANTLY
 INSTALLED LUMINAIRES. PLEASE CORRECT AS APPLICABLE.
  
 NEC 404.14 RATING AND USE OF SWITCHES.
 (E) DIMMER SWITCHES.
 GENERAL-USE DIMMER SWITCHES SHALL BE USED ONLY TO
 CONTROL PERMANENTLY INSTALLED INCANDESCENT LUMINAIRES
 UNLESS LISTED FOR THE CONTROL OF OTHER LOADS AND
 INSTALLED ACCORDINGLY.
  
 5) PLEASE INDICATE TAMPER RESISTANT RECEPTACLES IN ALL
 APPLICABLE LOCATIONS, IN ACCORDANCE WITH NEC 406.12(6)
 REFERRED TO IN 518.2 ASSEMBLY AREAS.
  
 406.12 TAMPER-RESISTANT RECEPTACLES.
 ALL 15- AND 20-AMPERE, 125- AND 250-VOLT
 NONLOCKING-TYPE RECEPTACLES IN THE AREAS SPECIFIED IN
 406.12(1) THROUGH (7) SHALL BE LISTED TAMPER-RESISTANT
 RECEPTACLES.
 (6) SUBSET OF ASSEMBLY OCCUPANCIES DESCRIBED IN 518.2
 TO INCLUDE PLACES OF WAITING TRANSPORTATION,
 GYMNASIUMS, SKATING RINKS, AND AUDITORIUMS
  
 2) PLEASE PROVIDE A NOTE STATING SIGNS AND ALL LOW
 VOLTAGE WIRING INCLUDING BUT NOT LIMITED TO, VOICE,
 DATA, AUDIO, VIDEO, SECURITY, ACCESS, POS, FIRE ALARM,
 ETC. REQUIRE A SEPARATE PERMIT.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  
  