2023-07-05 13:25:45 | ELECTRIC REVIEW FAILED |
| |
| 1) ROOMS LABELED WORKROOM A, B AND BACK BAR APPEAR TO |
| BE CLASSIFIED AS A KITCHEN IN ACCORDANCE WITH NEC 100 |
| DEFINITIONS. EQUIPMENT DETAILED ON KITCHEN EQUIPMENT |
| SCHEDULE DETAIL THEY ARE TO TERMINATE TO RECEPTACLES |
| WHICH ARE REQUIRED TO BE GFIC PROTECTED IN ACCORDANCE |
| WITH NEC 210.8. PLEASE CORRECT PLANS TO INDICATE ALL |
| RECEPTACLES LOCATED IN THESE KITCHEN AREAS COMPLY WITH |
| NEC 210.8 |
| |
| NEC 210.8 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION |
| FOR PERSONNEL |
| (B) OTHER THAN DWELLING UNITS. |
| ALL SINGLE-PHASE RECEPTACLES RATED 150 VOLTS TO GROUND |
| OR LESS, 50 AMPERES OR LESS AND THREE-PHASE RECEPTACLES |
| RATED 150 VOLTS TO GROUND OR LESS, 100 AMPERES OR LESS |
| INSTALLED IN THE FOLLOWING LOCATIONS SHALL HAVE |
| GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR |
| PERSONNEL. |
| (2) KITCHENS |
| |
| NEC 100 DEFINITIONS |
| KITCHEN. |
| AN AREA WITH A SINK AND PERMANENT PROVISIONS FOR FOOD |
| PREPARATION AND COOKING |
| |
| 3) SHEET E202 REFERS, INCORRECTLY TO A DETAIL ON SHEET |
| E 301 DETAIL 7 THAT APPEARS TO BE SHOWN ON SHEET E 302 |
| DETAIL 7. PLEASE CORRECT AS APPLICABLE. FBC 107.2 |
| |
| 4) SHEET E 303 DETAIL 2, BANQUET CLOSTER INDICATES A |
| DIMMED DUPLEX RECEPTACLE. NEC 404.14 STATES GENERAL USE |
| DIMMER SWITCHES SHALL ONLY BE USED TO CONTROL PERMANTLY |
| INSTALLED LUMINAIRES. PLEASE CORRECT AS APPLICABLE. |
| |
| NEC 404.14 RATING AND USE OF SWITCHES. |
| (E) DIMMER SWITCHES. |
| GENERAL-USE DIMMER SWITCHES SHALL BE USED ONLY TO |
| CONTROL PERMANENTLY INSTALLED INCANDESCENT LUMINAIRES |
| UNLESS LISTED FOR THE CONTROL OF OTHER LOADS AND |
| INSTALLED ACCORDINGLY. |
| |
| 5) PLEASE INDICATE TAMPER RESISTANT RECEPTACLES IN ALL |
| APPLICABLE LOCATIONS, IN ACCORDANCE WITH NEC 406.12(6) |
| REFERRED TO IN 518.2 ASSEMBLY AREAS. |
| |
| 406.12 TAMPER-RESISTANT RECEPTACLES. |
| ALL 15- AND 20-AMPERE, 125- AND 250-VOLT |
| NONLOCKING-TYPE RECEPTACLES IN THE AREAS SPECIFIED IN |
| 406.12(1) THROUGH (7) SHALL BE LISTED TAMPER-RESISTANT |
| RECEPTACLES. |
| (6) SUBSET OF ASSEMBLY OCCUPANCIES DESCRIBED IN 518.2 |
| TO INCLUDE PLACES OF WAITING TRANSPORTATION, |
| GYMNASIUMS, SKATING RINKS, AND AUDITORIUMS |
| |
| 2) PLEASE PROVIDE A NOTE STATING SIGNS AND ALL LOW |
| VOLTAGE WIRING INCLUDING BUT NOT LIMITED TO, VOICE, |
| DATA, AUDIO, VIDEO, SECURITY, ACCESS, POS, FIRE ALARM, |
| ETC. REQUIRE A SEPARATE PERMIT. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. |
| |
| CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2020 7TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| 7TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| V/R, |
| |
| MICHAEL PETERSON |
| ELECTRICAL PLANS EXAMINER |