Plan Review Notes For Permit 23041246 |
Permit Number |
23041246 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-05-01 12:15:10 | | | 1ST REVIEW FBC-2020 RES. GAS | | PERMIT- 23040946 | | 5/1/2023 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) GAS RISER: THE DRAWING IS NOT CONSISTENT WITH THE | | APPROVED RISER DRAWING AND INSPECTED GAS PIPING UNDER | | PERMITS- 06060668 & 08100085. PLEASE CORRECT THE | | DRAWING PER THE ITEMS BELOW. | | | | A) MISSING FROM THE NEW DRAWING IS THE 2-INCH LOW | | PRESSURE PE LINE TO THE 400,000 BTU POOL HEATER. THE | | LENGTH OF THE PIPE RUN FROM THE METER RISER IS 35 FT. 2 | | INCHES. | | | | B) THE NEW DRAWING SHOWS A 3/4-INCH GALV. PIPE INTO THE | | STRUCTURE HOWEVER THE APPROVED DRAWING SHOWS AN | | 1-1/4-INCH. | | | | C) BASED ON THE APPROVED DRAWING THE NEW TOTAL LOAD OF | | THE SYSTEM IS 986,000 BTUS- INTERIOR- 272,000, POOL | | HEATER- 400,000, AND GENERATOR- 314,000. | | | | 2) THE GENERATOR EXHAUST SHALL BE MINIMUM 10 FT. AWAY | | FROM OPENINGS INTO THE BUILDING. PLEASE CORRECT THE 5 | | FT. NOTE ON THE SURVEY- SEC. R303.5.1 FBC RES. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|