Plan Review Notes For Permit 23041246
Permit Number 23041246
Review Stop G
Sequence Number 1
Notes
Date Text
2023-05-01 12:15:10 
 1ST REVIEW FBC-2020 RES. GAS
 PERMIT- 23040946
 5/1/2023
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS RISER: THE DRAWING IS NOT CONSISTENT WITH THE
 APPROVED RISER DRAWING AND INSPECTED GAS PIPING UNDER
 PERMITS- 06060668 & 08100085. PLEASE CORRECT THE
 DRAWING PER THE ITEMS BELOW.
  
 A) MISSING FROM THE NEW DRAWING IS THE 2-INCH LOW
 PRESSURE PE LINE TO THE 400,000 BTU POOL HEATER. THE
 LENGTH OF THE PIPE RUN FROM THE METER RISER IS 35 FT. 2
 INCHES.
  
 B) THE NEW DRAWING SHOWS A 3/4-INCH GALV. PIPE INTO THE
 STRUCTURE HOWEVER THE APPROVED DRAWING SHOWS AN
 1-1/4-INCH.
  
 C) BASED ON THE APPROVED DRAWING THE NEW TOTAL LOAD OF
 THE SYSTEM IS 986,000 BTUS- INTERIOR- 272,000, POOL
 HEATER- 400,000, AND GENERATOR- 314,000.
  
 2) THE GENERATOR EXHAUST SHALL BE MINIMUM 10 FT. AWAY
 FROM OPENINGS INTO THE BUILDING. PLEASE CORRECT THE 5
 FT. NOTE ON THE SURVEY- SEC. R303.5.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  