Plan Review Notes
Plan Review Notes For Permit 23041244
Permit Number 23041244
Review Stop P
Sequence Number 1
Notes
Date Text
2023-04-25 06:46:211ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMENDS 107.2.1 - PER OUR CONVERSATION ON
 SITE, THIS SINK WAS NOT PERMITTED AND A FULL REVIEW OF
 ALL CONNECTION IS REQUIRED. THIS PERMIT IS NOT SIMPLY
 FOR THE INSTALLATION OF THE VENT REQUIRED. IT IS FOR
 THE INSTALLATION OF A SINK WHERE THERE WAS NO SINK TO
 BEGIN WITH. SHOW A DRAIN AND VENT DIAGRAM THAT INCLUDES
 THE CONNECTIONS TO THE EXISTING SYSTEM IN COMPLIANCE
 WITH THE PLUMBING CODE. INCLUDE A SIMPLE FLOOR PLAN
 THAT SHOWS THE LOCATION OF THE SINK INSTALLED.
  
 2. 2020 FRC P3108.1 - THE SINK CANNOT BE INCLUDED IN
 THE WET VENT.
  
 3. 2017 WPB AMENDS 107.2.1. - THE PERSON WHO DESIGNS
 THE DRAWING IS REQUIRED TO SIGN THE DRAWING.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  