2023-05-02 15:37:58 | 1ST REVIEW FBC-2020 RES. GAS |
| PERMIT- 23041206 |
| 5/2/23 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET PG-1: PLEASE DO NOT USE THE PHRASE (EITHER OR) |
| CONCERNING THE TYPE OF GAS PIPING TO BE INSTALLED. EACH |
| TYPE OF PIPING HAS LIMITIATIONS OF USE. IDENTIFY OR |
| LABEL EACH SEGMENT OF PIPING SHOWN ON THE PLAN AND IN |
| THE RISER DRAWING- SECS. G2414.4 & G2414.6 FBC RES. |
| PLEASE NOTE UNPROTECTED STEEL PIPE SHALL NOT BE RUN |
| UNDERGROUND, AND PE PIPING SHALL NOT BE RUN UNDER ANY |
| BUILDING OR SLAB- SECS. G2415.11 & G2415.17.1. |
| |
| 2) PG-1: BASED ON THE SCHEDULE 40 METALLIC LOW PRESSURE |
| PIPE SIZING TABLE IN THE FBC RES- TABLES G2413.4(1) THE |
| ??-INCH PIPE SUPPLYING THE WATER HEATER SHALL BE |
| INCREASED TO 1-INCH. |
| |
| 3) PG-1: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE |
| RANGE- SEC. G2407.1 FBC RES. IF USING THE STANDARD |
| INDOOR AIR METHOD THE MINIMUM REQUIRED VOLUME SHALL 50 |
| CU.FT. PER 1000 BTU OF THE RANGE INPUT RATING- SEC. |
| G2407.5 FBC RES. |
| |
| 4) PG-1: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE |
| DRYER- SEC. G2407.1 FBC RES. PLEASE NOTE THE EXCEPTION |
| WHICH ALLOWS FOR MAKEUP AIR TO BE SUBSTITUTED IN |
| ACCORDANCE WITH SEC. G2439.5. |
| |
| 5) PG-1: SHOW A MINIMUM 4 FT. CLEARANCE FOR THE WATER |
| HEATER EXHAUST TO THE WINDOWS AND DOORS- SECS. G2427.8 |
| & G2448.1 FBC RES. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| [email protected] |
| |