Plan Review Notes
Plan Review Notes For Permit 23041206
Permit Number 23041206
Review Stop G
Sequence Number 1
Notes
Date Text
2023-05-02 15:37:581ST REVIEW FBC-2020 RES. GAS
 PERMIT- 23041206
 5/2/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET PG-1: PLEASE DO NOT USE THE PHRASE (EITHER OR)
 CONCERNING THE TYPE OF GAS PIPING TO BE INSTALLED. EACH
 TYPE OF PIPING HAS LIMITIATIONS OF USE. IDENTIFY OR
 LABEL EACH SEGMENT OF PIPING SHOWN ON THE PLAN AND IN
 THE RISER DRAWING- SECS. G2414.4 & G2414.6 FBC RES.
 PLEASE NOTE UNPROTECTED STEEL PIPE SHALL NOT BE RUN
 UNDERGROUND, AND PE PIPING SHALL NOT BE RUN UNDER ANY
 BUILDING OR SLAB- SECS. G2415.11 & G2415.17.1.
  
 2) PG-1: BASED ON THE SCHEDULE 40 METALLIC LOW PRESSURE
 PIPE SIZING TABLE IN THE FBC RES- TABLES G2413.4(1) THE
 ??-INCH PIPE SUPPLYING THE WATER HEATER SHALL BE
 INCREASED TO 1-INCH.
  
 3) PG-1: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 RANGE- SEC. G2407.1 FBC RES. IF USING THE STANDARD
 INDOOR AIR METHOD THE MINIMUM REQUIRED VOLUME SHALL 50
 CU.FT. PER 1000 BTU OF THE RANGE INPUT RATING- SEC.
 G2407.5 FBC RES.
  
 4) PG-1: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 DRYER- SEC. G2407.1 FBC RES. PLEASE NOTE THE EXCEPTION
 WHICH ALLOWS FOR MAKEUP AIR TO BE SUBSTITUTED IN
 ACCORDANCE WITH SEC. G2439.5.
  
 5) PG-1: SHOW A MINIMUM 4 FT. CLEARANCE FOR THE WATER
 HEATER EXHAUST TO THE WINDOWS AND DOORS- SECS. G2427.8
 & G2448.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  