Plan Review Notes
Plan Review Notes For Permit 23041099
Permit Number 23041099
Review Stop NFIP
Sequence Number 1
Notes
Date Text
2023-06-22 11:01:17NFIP REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) IN ITEM A9 C) THE TOTAL NET OPENING FOR THE
 ENGINEERED FLOOD VENTS SHOULD BE 800 SQUARE INCHES
 WHICH IS EQUILALENT TO THE 800 SQUARE FEET OF AREA THE
 ENGINEERED VENTS ARE RATED FOR. SEE FEMA NFIP TECHNICAL
 BULLETIN 1 SECTION 9.3.5
  
 2) THE ATTACHMENT BOX SHOULD BE CHECKED IN SECTION D
 AND THE EVALUATION REPORTS FOR THE ENGINEERED FLOOD
 VENTS SHOULD BE ATTACHED. THE EVALUATIONS NEED TO
 SPECIFY THE COVERAGE AREA RATING OF THE VENTS. NOTE:
 THE PRODUCT APPROVALS THAT WERE SUBMITTED DO NOT.
  
 3) THE COMMENT AREA OF SECTION D NEEDS TO INCLUDE THE
 ENGINEERED FLOOD VENTS MODEL NUMBERS AND COVERAGE AREA
 CAPACITY. IT SHOULD BE NOTED THAT THE INTERIOR GRADE
 ELEVATION OF THE GARAGE WAS USED TO DETERMINE THE
 ELEVATION OF THE THE ENGINEERED FLOOD VENTS. SEE THE
 ELEVATION CERTIFICATE INSTRUCTIONS AND NOTES ON THE
 FLOOR PLAN.
  
  