Plan Review Notes For Permit 23041099 |
Permit Number |
23041099 |
|
Review Stop |
NFIP |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-06-22 11:01:17 | NFIP REVIEW COMMENTS | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) IN ITEM A9 C) THE TOTAL NET OPENING FOR THE | | ENGINEERED FLOOD VENTS SHOULD BE 800 SQUARE INCHES | | WHICH IS EQUILALENT TO THE 800 SQUARE FEET OF AREA THE | | ENGINEERED VENTS ARE RATED FOR. SEE FEMA NFIP TECHNICAL | | BULLETIN 1 SECTION 9.3.5 | | | | 2) THE ATTACHMENT BOX SHOULD BE CHECKED IN SECTION D | | AND THE EVALUATION REPORTS FOR THE ENGINEERED FLOOD | | VENTS SHOULD BE ATTACHED. THE EVALUATIONS NEED TO | | SPECIFY THE COVERAGE AREA RATING OF THE VENTS. NOTE: | | THE PRODUCT APPROVALS THAT WERE SUBMITTED DO NOT. | | | | 3) THE COMMENT AREA OF SECTION D NEEDS TO INCLUDE THE | | ENGINEERED FLOOD VENTS MODEL NUMBERS AND COVERAGE AREA | | CAPACITY. IT SHOULD BE NOTED THAT THE INTERIOR GRADE | | ELEVATION OF THE GARAGE WAS USED TO DETERMINE THE | | ELEVATION OF THE THE ENGINEERED FLOOD VENTS. SEE THE | | ELEVATION CERTIFICATE INSTRUCTIONS AND NOTES ON THE | | FLOOR PLAN. | | | | |
|