Plan Review Notes
Plan Review Notes For Permit 23041044
Permit Number 23041044
Review Stop B
Sequence Number 3
Notes
Date Text
2023-06-21 12:56:07JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC B 107.2.1. PROVIDE THE FOLLOWING INFORMATION FOR
 FLORIDA PRODUCT APPROVAL FL14083-R28 FOR THE PROPOSED
 FLAT ROOF RECOVER SYSTEM TO BE USED CORRESPONDING TO
 ENGINEERS MEMBRANE ATTACHMENT CALCULATIONS. EVALUATION
 REPORT PAGES #1-5, INSTALLATION INSTRUCTIONS FOR SYSTEM
 R-79 PAGE #97. ALL APPLICABLE DETAILS AND ATTACHMENTS
 MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL
 DRAWINGS. SUBMITTED EVALUATION REPORT & INSTALLATION
 INSTRUCTIONS ARE FOR FL14083-R26.
 2. FBC R 301 FAC9N-3. PROVIDE REROOF SYSTEM NUMBER &
 INSTALLATION INSTRUCTIONS PAGE FOR THE MAIN CENTER ROOF
 & LOWER NORTH ROOF AREAS TO BE REMOVED AND REPLACED AS
 PER THE SUBMITTED ROOF MOISTURE REPORT. PROVIDE SIGNED
 AND SEALED CALCULATIONS IF SYSTEM SELECTED DOES NOT
 MEET MINIMUM DESIGN PRESSURE REQUIREMENTS. PLEASE NOTE:
 PRODUCT APPROVAL FL14083-R28 WAS REVISED TO FL14083-R29
 ON JUNE 20, 2023.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  