| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| |
| 1. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL16440-R24 |
| (HVHZ) IS NOT APPROVED FOR USE OUTSIDE HVHZ. CITY OF |
| WEST PALM BEACH IS NOT LOCATED IN A HVHZ. YOU MIGHT |
| CONSIDER USING FL14083-R28 (NON-HVHZ). PROVIDE THE |
| FOLLOWING: COVER PAGE, EVALUATION REPORTS PAGES 1-5 TO |
| INCLUDE LIMITATIONS PAGE(S) AND INSTALLATION |
| INSTRUCTIONS FOR SYSTEM USED. SELECT SYSTEM THAT MEETS |
| OR EXCEEDS EXPOSURE CATEGORY C MINIMUM DESIGN PRESSURE |
| ZONE 3 REQUIREMENTS OF -108.17. SIGNED AND SEALED |
| NAILING CALCULATIONS MAY BE REQUIRED. |
| 2. PROVIDE FIELD UPLIFT TESTING IN ACCORDANCE WITH |
| TESTING APPLICATION STANDARD TAS 124 AS REQUIRED BY |
| LIMITATIONS 5.6.1 OF PRODUCT APPROVAL FL14083. |
| 3. FBC EB 706.3(1) PROVIDE A SIGNED AND SEALED MOISTURE |
| REPORT PREPARED BY A FLORIDA REGISTERED DESIGN |
| PROFESSIONAL. |
| 4. FBC B 107.2.1 PROVIDE A SIGN AND SEALED ROOF |
| DRAINAGE PLAN THAT COMPLIES WITH SECTION 1503 OF THE |
| 2020 FBC-BUILDING AND CHAPTER 11 OF THE 2020 |
| FBC-PLUMBING. |
| 5. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF |
| DIAGRAM/SKETCH AND SHOW THE AREAS TO RECEIVE NEW |
| ROOFING CLEARLY IDENTIFIED ON DRAWING; INCLUDE ROOF |
| SLOPE(S), MEAN ROOF HEIGHT(S). |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |