Notes
Date Text
2023-04-21 11:44:151ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMENDS 107.3.5.1.3 - PLEASE INCLUDE A
 PLUMBING PLAN THAT SHOWS THE NEW FIXTURES AND THEIR
 INTENDED CONNECTIONS TO THE SANITARY SYSTEM.
  
 2. 2020 FPC 315.1 - AS A NOTE - NEW PENETRATIONS IN THE
 FLOORS, WALLS, OR CEILING AS WELL AS ABANDONED
 PENETRATIONS WILL NEED A UL LISTED FIRE STOPPING DETAIL
 SUBMITTED AND REVIEWED BY THE BUILDING REVIEW AND
 SHOULD BE INCLUDED IN THE A PAGES.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  