Plan Review Notes For Permit 23040946 |
Permit Number |
23040946 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-05-02 10:12:32 | PETER E VALENTI | | BUILDING PLANS EXAMINER II/INSPECTOR | | [email protected] | | 561 805 6673 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC M = FBC MECHANICAL | | FBC FG = FBC FUEL GAS | | | | BUILDING REVIEW DENIED: | | | | 1.) FBC B 107.2.1,PROVIDE AN ENGINEER'S LETTER WITH THE | | X-RAY REPORT SHOWING THE SLAB PENETRATION CLEARANCE OF | | EXISTING REINFORCEMENT/P.T. CABLES FOR THE NEW SHOWER | | DRAIN. | | | | 2.) FBC 603.1,(ITEM 2, EXCEPTION 2), PROVIDE THE FLAME | | SPREAD TEST REPORT FOR FLOORING UNDERLAYMENT. ALLOWABLE | | MATERIALS IN NON COMBUSTIBLE BUILDINGS, ACOUSTICAL | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE | | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 | | OR UL 723. | | | | 3.) CITY OF WPB AMENDMENTS TO FBC B 107.2.1, PROVIDE | | THE CONTRACTOR'S SIGNATURE ON ALL SUBMITTED PLAN SHEETS | | BY THE CONTRACTOR. | | |
|