2023-06-05 15:49:29 | RESIDENTIAL REROOF SECOND BUILDING REVIEW COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #23040933 |
| 523 HAMPTON RD |
| |
| 1- MISSING FLAT ROOF PRODUCT APPROVAL. PROVIDE PRODUCT |
| APPROVAL FOR FLAT ROOF AS REQUIRED BY FAC 61G20-3.001 |
| AND CLEARLY MARK WHICH APPROVED ASSEMBLY IS GOING TO BE |
| INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN |
| PRESSURES OF SEC. R301.2.1 FBC-RESIDENTIAL. NOTE: IF |
| THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES |
| FOR ALL ROOF ZONES, THEN SIGNED AND SEALED RAS 117 |
| CALCULATIONS ARE REQUIRED. |
| NOTE: NAIL ENHANCEMENT CALCULATIONS SUBMITTED ARE USING |
| THE OLD CODE. DESIGN PROFESSIONAL NEEDS TO USE THE |
| CURRENT 2020 CODE AND NEED TO SPECIFY THE DIMENSIONS |
| FOR EACH ROOF ZONE AS REQUIRED BY FIGURE |
| R301.2(7)FBC-RESIDENTIAL. |
| |
| RESPONSE: |
| FLAT ROOF NOA 18-0919.12 WAS SUBMITTED BUT THE RAS 117 |
| NAIL ENHANCEMENT CALCULATIONS WERE NOT REVISED. DESIGN |
| PROFESSIONAL NEEDS TO USE THE CURRENT 2020 CODE AND |
| NEED TO SPECIFY THE DIMENSIONS FOR EACH NEW ROOF ZONE |
| AS REQUIRED BY FIGURE R301.2(7)FBC-RESIDENTIAL. PROVIDE |
| ROOF SKETCH SHOWING THE DIMENSIONS FOR EACH NEW ROOF |
| ZONE.. |
| NOTE: THERE ARE 4 NEW ROOF ZONES. SEE FIGURE |
| R301.2(7)FBC-RESIDENTIAL. ALSO, REVISE CALCULATIONS TO |
| INCLUDE THE DESIGN PRESSURES FOR EACH ROOF ZONE. |
| |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |
| [email protected] |