2023-06-05 15:49:29RESIDENTIAL REROOF SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #23040933
 523 HAMPTON RD
  
 1- MISSING FLAT ROOF PRODUCT APPROVAL. PROVIDE PRODUCT
 APPROVAL FOR FLAT ROOF AS REQUIRED BY FAC 61G20-3.001
 AND CLEARLY MARK WHICH APPROVED ASSEMBLY IS GOING TO BE
 INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301.2.1 FBC-RESIDENTIAL. NOTE: IF
 THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES
 FOR ALL ROOF ZONES, THEN SIGNED AND SEALED RAS 117
 CALCULATIONS ARE REQUIRED.
 NOTE: NAIL ENHANCEMENT CALCULATIONS SUBMITTED ARE USING
 THE OLD CODE. DESIGN PROFESSIONAL NEEDS TO USE THE
 CURRENT 2020 CODE AND NEED TO SPECIFY THE DIMENSIONS
 FOR EACH ROOF ZONE AS REQUIRED BY FIGURE
 R301.2(7)FBC-RESIDENTIAL.
  
 RESPONSE:
 FLAT ROOF NOA 18-0919.12 WAS SUBMITTED BUT THE RAS 117
 NAIL ENHANCEMENT CALCULATIONS WERE NOT REVISED. DESIGN
 PROFESSIONAL NEEDS TO USE THE CURRENT 2020 CODE AND
 NEED TO SPECIFY THE DIMENSIONS FOR EACH NEW ROOF ZONE
 AS REQUIRED BY FIGURE R301.2(7)FBC-RESIDENTIAL. PROVIDE
 ROOF SKETCH SHOWING THE DIMENSIONS FOR EACH NEW ROOF
 ZONE..
 NOTE: THERE ARE 4 NEW ROOF ZONES. SEE FIGURE
 R301.2(7)FBC-RESIDENTIAL. ALSO, REVISE CALCULATIONS TO
 INCLUDE THE DESIGN PRESSURES FOR EACH ROOF ZONE.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,