Plan Review Notes
Plan Review Notes For Permit 23040885
Permit Number 23040885
Review Stop B
Sequence Number 3
Notes
Date Text
2023-05-08 13:49:51RESIDENTIAL (R2) THIRD BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #23040885
 300 S AUSTRALIAN AVE # 1119
  
 1- OK.
 2- OK.
 3- OK.
  
 ORIGINAL COMMENT:
 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES (IF ANY) AS REQUIRED BY SEC. 109.3
 CITY AMENDMENTS. UPDATE VALUATION TO INCLUDE ALL COSTS
 OR PROVIDE COMPLETE COST BREAKDOWN INCLUDING DESIGN
 PROFESSIONAL FEES (IF ANY).
  
 RESPONSE:
 VALUE WAS UPDATED TO $6, 120. OWES $92.64.
  
 5)NOTICE OF COMMENCEMENT
 - NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
  
  
 6- FLOORING SOUND INSULATION MATERIAL:
  
 PREVIOUS COMMENT:
 (B)PROFLEX MSC-90 COPY OF THE SOUND TRANSMISSION CLASS
 (STC) SUBMITTED IS FOR TILE INSTALLATION. CONTRACTOR
 NEEDS TO SUBMIT COPY OF TEST FOR LAMINATED WOOD FLOOR.
 SEC. 1207.2 OF FBC 7TH EDITION (2020).
 NOTE: THIS BUILDING DOESN'T HAVE 8" CONCRETE SLAB.
 SUBMIT TEST FOR 7" CONCRETE SLAB OR LESS.
  
 RESPONSE:
 THERE ARE TWO DIFFERENT TESTS SUBMITTED FOR LV200
 UNDERLAYMENT. ONE IS FOR 12MM LAMINATED WOOD AND THE
 OTHER ONE IS FOR 4MM LUXURY VINYL PLANK. NONE OF THESE
 TESTS MATCH PROPOSED FINISH FLOORING. CONTRACTOR
 SUBMITTED SPECIFICATIONS FOR JESSAMINE OAK 7MM
 LAMINATED WOOD FLOORING. NEED TO PROVIDE TEST FOR 7MM
 THAT MATCHES PROPOSED INSTALLATION.
 NOTE:
 CONTRACTOR ALSO SUBMITTED TEST FOR PROFLEX SUPER SIM 90
 UNDERLAYMENT ON A 6 INCH CONCRETE SLAB. THIS TEST
 CANNOT BE USED BECAUSE THIS TEST IS FOR TILE
 INSTALLATION NOT FOR LAMINATED FLOORING AS SPECIFIED BY
 THE CONTRACTOR.
  
 PREVIOUS COMMENT:
 (C)PROFLEX MSC-90 COPY OF THE IMPACT INSULATION CLASS
 (IIC) SUBMITTED IS FOR TILE INSTALLATION. CONTRACTOR
 NEEDS TO SUBMIT COPY OF TEST FOR LAMINATED WOOD FLOOR.
 SEC. 1207.3 OF FBC 7TH EDITION (2020).
 NOTE: THIS BUILDING DOESN'T HAVE 8" CONCRETE SLAB.
 SUBMIT TEST FOR 7" CONCRETE SLAB OR LESS.
  
 RESPONSE:
 THERE ARE TWO DIFFERENT TESTS SUBMITTED FOR LV200
 UNDERLAYMENT. ONE IS FOR 12MM LAMINATED WOOD AND THE
 OTHER ONE IS FOR 4MM LUXURY VINYL PLANK. NONE OF THESE
 TESTS MATCH PROPOSED FINISH FLOORING. CONTRACTOR
 SUBMITTED SPECIFICATIONS FOR JESSAMINE OAK 7MM
 LAMINATED WOOD FLOORING. NEED TO PROVIDE TEST FOR 7MM
 THAT MATCHES PROPOSED INSTALLATION.
 NOTE:
 CONTRACTOR ALSO SUBMITTED TEST FOR PROFLEX SUPER SIM 90
 UNDERLAYMENT ON A 6 INCH CONCRETE SLAB. THIS TEST
 CANNOT BE USED BECAUSE THIS TEST IS FOR TILE
 INSTALLATION NOT FOR LAMINATED FLOORING AS SPECIFIED BY
 THE CONTRACTOR.
  
  
 NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR CONSTRUCTION
 (WOOD TRUSSES/JOISTS OR CONCRETE SLAB) AND PROPOSED
 FLOOR FINISH.
 NOTE: THERE ARE TESTS FOR 6" OR 8" CONCRETE SLABS WITH
 OR WITHOUT ACOUSTICAL CEILING. TYPICALLY THERE ARE NOT
 SUSPENDED ACOUSTICAL CEILINGS IN THESE BUILDINGS.
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT).
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  