2023-05-08 13:49:51 | RESIDENTIAL (R2) THIRD BUILDING REVIEW COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #23040885 |
| 300 S AUSTRALIAN AVE # 1119 |
| |
| 1- OK. |
| 2- OK. |
| 3- OK. |
| |
| ORIGINAL COMMENT: |
| 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN |
| PROFESSIONAL FEES (IF ANY) AS REQUIRED BY SEC. 109.3 |
| CITY AMENDMENTS. UPDATE VALUATION TO INCLUDE ALL COSTS |
| OR PROVIDE COMPLETE COST BREAKDOWN INCLUDING DESIGN |
| PROFESSIONAL FEES (IF ANY). |
| |
| RESPONSE: |
| VALUE WAS UPDATED TO $6, 120. OWES $92.64. |
| |
| 5)NOTICE OF COMMENCEMENT |
| - NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| FLORIDA STATUTE. |
| |
| |
| 6- FLOORING SOUND INSULATION MATERIAL: |
| |
| PREVIOUS COMMENT: |
| (B)PROFLEX MSC-90 COPY OF THE SOUND TRANSMISSION CLASS |
| (STC) SUBMITTED IS FOR TILE INSTALLATION. CONTRACTOR |
| NEEDS TO SUBMIT COPY OF TEST FOR LAMINATED WOOD FLOOR. |
| SEC. 1207.2 OF FBC 7TH EDITION (2020). |
| NOTE: THIS BUILDING DOESN'T HAVE 8" CONCRETE SLAB. |
| SUBMIT TEST FOR 7" CONCRETE SLAB OR LESS. |
| |
| RESPONSE: |
| THERE ARE TWO DIFFERENT TESTS SUBMITTED FOR LV200 |
| UNDERLAYMENT. ONE IS FOR 12MM LAMINATED WOOD AND THE |
| OTHER ONE IS FOR 4MM LUXURY VINYL PLANK. NONE OF THESE |
| TESTS MATCH PROPOSED FINISH FLOORING. CONTRACTOR |
| SUBMITTED SPECIFICATIONS FOR JESSAMINE OAK 7MM |
| LAMINATED WOOD FLOORING. NEED TO PROVIDE TEST FOR 7MM |
| THAT MATCHES PROPOSED INSTALLATION. |
| NOTE: |
| CONTRACTOR ALSO SUBMITTED TEST FOR PROFLEX SUPER SIM 90 |
| UNDERLAYMENT ON A 6 INCH CONCRETE SLAB. THIS TEST |
| CANNOT BE USED BECAUSE THIS TEST IS FOR TILE |
| INSTALLATION NOT FOR LAMINATED FLOORING AS SPECIFIED BY |
| THE CONTRACTOR. |
| |
| PREVIOUS COMMENT: |
| (C)PROFLEX MSC-90 COPY OF THE IMPACT INSULATION CLASS |
| (IIC) SUBMITTED IS FOR TILE INSTALLATION. CONTRACTOR |
| NEEDS TO SUBMIT COPY OF TEST FOR LAMINATED WOOD FLOOR. |
| SEC. 1207.3 OF FBC 7TH EDITION (2020). |
| NOTE: THIS BUILDING DOESN'T HAVE 8" CONCRETE SLAB. |
| SUBMIT TEST FOR 7" CONCRETE SLAB OR LESS. |
| |
| RESPONSE: |
| THERE ARE TWO DIFFERENT TESTS SUBMITTED FOR LV200 |
| UNDERLAYMENT. ONE IS FOR 12MM LAMINATED WOOD AND THE |
| OTHER ONE IS FOR 4MM LUXURY VINYL PLANK. NONE OF THESE |
| TESTS MATCH PROPOSED FINISH FLOORING. CONTRACTOR |
| SUBMITTED SPECIFICATIONS FOR JESSAMINE OAK 7MM |
| LAMINATED WOOD FLOORING. NEED TO PROVIDE TEST FOR 7MM |
| THAT MATCHES PROPOSED INSTALLATION. |
| NOTE: |
| CONTRACTOR ALSO SUBMITTED TEST FOR PROFLEX SUPER SIM 90 |
| UNDERLAYMENT ON A 6 INCH CONCRETE SLAB. THIS TEST |
| CANNOT BE USED BECAUSE THIS TEST IS FOR TILE |
| INSTALLATION NOT FOR LAMINATED FLOORING AS SPECIFIED BY |
| THE CONTRACTOR. |
| |
| |
| NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR CONSTRUCTION |
| (WOOD TRUSSES/JOISTS OR CONCRETE SLAB) AND PROPOSED |
| FLOOR FINISH. |
| NOTE: THERE ARE TESTS FOR 6" OR 8" CONCRETE SLABS WITH |
| OR WITHOUT ACOUSTICAL CEILING. TYPICALLY THERE ARE NOT |
| SUSPENDED ACOUSTICAL CEILINGS IN THESE BUILDINGS. |
| |
| PLEASE NOTE THAT TEST REPORTS ARE REQUIRED - |
| MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO |
| DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST |
| REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE |
| MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT). |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |
| [email protected] |
| |