2023-05-02 18:04:55 | RESIDENTIAL (R2)BUILDING REVIEW COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #23040885 |
| 300 S AUSTRALIAN AVE # 1119 |
| |
| 1- PROVIDE FLOOR PLAN SHOWING AREAS TO HAVE NEW |
| FLOORING. AND, SPECIFY FLOOR AREA OF EACH ROOM. SEC. |
| 107.2.1 CITY AMENDMENTS. |
| |
| 2- FINISH FLOOR MATERIAL TO BE INSTALLED IS NOT CLEAR. |
| PERMIT APPLICATION STATES " REMOVE CARPETS AND REPLACE |
| WITH VINYL FLOORING". CONTRACTOR UPLOADED |
| SPECIFICATIONS FOR LAMINATED WOOD FLOORS. CONTRACTOR TO |
| REVISE SCOPE OF WORK ON PERMIT APPLICATION TO MATCH |
| SPECIFICATIONS SUBMITTED. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 3- CONTRACTOR UPLOADED SPECIFICATIONS FOR LAMINATED |
| PLANKS WALL MOUNTING . PROVIDE FLOOR PLAN SHOWING AREAS |
| TO HAVE LAMINATED WALL PLANKS AND PROVIDE DETAILS |
| SHOWING WALLS AREAS TO BE COVERED. FULL WALL, PARTIAL |
| WALL, ETC.? SPECIFY FLOOR AREA OF EACH ROOM. SEC. |
| 107.2.1 CITY AMENDMENTS. |
| |
| 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN |
| PROFESSIONAL FEES (IF ANY) AS REQUIRED BY SEC. 109.3 |
| CITY AMENDMENTS. UPDATE VALUATION TO INCLUDE ALL COSTS |
| OR PROVIDE COMPLETE COST BREAKDOWN INCLUDING DESIGN |
| PROFESSIONAL FEES (IF ANY). |
| |
| 5- FLOORING SOUND INSULATION MATERIAL: |
| (A)PROFLEX SUPER SIM-90 COPY OF THE FLAME SPREAD INDEX |
| AND SMOKE DEVELOPED INDEX TEST SUBMITTED IS FOR TILE |
| INSTALLATION. CONTRACTOR NEEDS TO SUBMIT COPY OF TEST |
| FOR LAMINATED WOOD FLOOR. (NOTE: UNDERLAYMENT PRODUCT |
| TO MATCH UNDERLAYMENT USED ON REQUIRED TESTS BELOW). |
| SEC. 720.1 AND 720.2 OF FBC 7TH EDITION (2020). |
| |
| (B)PROFLEX MSC-90 COPY OF THE SOUND TRANSMISSION CLASS |
| (STC) SUBMITTED IS FOR TILE INSTALLATION. CONTRACTOR |
| NEEDS TO SUBMIT COPY OF TEST FOR LAMINATED WOOD FLOOR. |
| SEC. 1207.2 OF FBC 7TH EDITION (2020). |
| NOTE: THIS BUILDING DOESN'T HAVE 8" CONCRETE SLAB. |
| SUBMIT TEST FOR 7" CONCRETE SLAB OR LESS. |
| |
| (C)PROFLEX MSC-90 COPY OF THE IMPACT INSULATION CLASS |
| (IIC) SUBMITTED IS FOR TILE INSTALLATION. CONTRACTOR |
| NEEDS TO SUBMIT COPY OF TEST FOR LAMINATED WOOD FLOOR. |
| SEC. 1207.3 OF FBC 7TH EDITION (2020). |
| NOTE: THIS BUILDING DOESN'T HAVE 8" CONCRETE SLAB. |
| SUBMIT TEST FOR 7" CONCRETE SLAB OR LESS. |
| |
| |
| NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR CONSTRUCTION |
| (WOOD TRUSSES/JOISTS OR CONCRETE SLAB) AND PROPOSED |
| FLOOR FINISH. |
| NOTE: THERE ARE TESTS FOR 6" OR 8" CONCRETE SLABS WITH |
| OR WITHOUT ACOUSTICAL CEILING. TYPICALLY THERE ARE NOT |
| SUSPENDED ACOUSTICAL CEILINGS IN THESE BUILDINGS. |
| |
| PLEASE NOTE THAT TEST REPORTS ARE REQUIRED - |
| MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO |
| DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST |
| REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE |
| MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT). |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |