2023-05-18 08:43:57 | 1ST NFIP REVIEW |
| RESULTS: CORRECTIONS NEEDED |
| |
| CHRISTOPHER S. THROOP, CBO, BN, PX, CFM |
| PLANS EXAMINER II |
| CITY OF WEST PALM BEACH |
| (561) 805-6726 |
| [email protected] |
| |
| CODES IN EFFECT: |
| 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| CITY ORDINANCE NO. 4658-16 AND NO. 4729-17 |
| FEMA DESK REFERENCE P 758 |
| FBC R322 FLOOD-RESISTANT CONSTRUCTION |
| |
| NOTICE: THIS PROJECT IS LOCATED IN A SPECIAL FLOOD |
| HAZARD AREA (SFHA). THE FLOOD ZONE DESIGNATION FOR THIS |
| SITE IS AE 6 AND AE 7 WITH BASE FLOOD ELEVATIONS (BFE) |
| OF 6'0" NAVD AND 7'0" NAVD. |
| THE CITY OF WEST PALM BEACH (THROUGH ORDINANCE NO. |
| 4729-17) REQUIRES AN ADDITIONAL 24 INCHES OF FREEBOARD. |
| THE DESIGN FLOOD ELEVATION (DFE) SHALL BE AT OR ABOVE |
| 9'0" NAVD. |
| |
| BUILDING UNDER CONSTRUCTION EC |
| |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT: |
| |
| 1. LINES A8 B) & C) SHALL BE N/A PER EC INSTRUCTIONS. |
| |
| 2. LINE A9 B) IS MISSING DATA. (PROPOSED) |
| |
| 3. LINE A9 C) IS MISSING DATA. NOTE: TOTAL NET AREA OF |
| SMART VENTS - (USE FEMA TECHNICAL BULLITEN #1 SECTION |
| 9.PG. 39) (PROPOSED) |
| |
| 4. LINE A9 D) IS MISSING DATA. (PROPOSED) |
| |
| 5. LINE C2 A) STATES LOWEST FLOOR IS 10.0'. FORM BOARD |
| SURVEY SHOWS LOWEST FORM IS 9.41'. PLEASE CLARIFY? |
| |
| 6. LINE A9 A) EC STATES GARAGE IS 1074.0 SF. PLANS |
| INDICATE GARAGE IS 1091 SF, PLEASE CLARIFY? |
| |
| 7. LINE C2 E) IS MISSING DATA. |
| |
| 8. COMMENTS IN SECTION D SHALL INCLUDE TYPE OF |
| EQUIPMENT AND LOCATION, PER C2 E). (PROPOSED) |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |