Plan Review Notes
Plan Review Notes For Permit 23040751
Permit Number 23040751
Review Stop B
Sequence Number 2
Notes
Date Text
2023-05-25 08:37:28PETER E VALENTI
 BUILDING PLANS EXAMINER II/INSPECTOR
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 1.) FBC B 107.2.1, PLEASE INDICATE, ON-PLAN, THE
 LOCATION OF WINDOWS/DOORS TO BE INSTALLED. INCLUDE THE
 TYPE AND SIZE OF WINDOWS/DOORS TO BE INSTALLED ON THE
 PLAN. ALSO, THE ONLY NOA/PRODUCT APPROVAL SUBMITTED WAS
 FOR THE FIXED WINDOWS (22-0105.01). ARE THERE OTHER
 TYPES OF WINDOWS/DOORS THAT ARE TO BE INSTALLED?
  
 2.) FBC B 107.2.1, PROVIDE THE PRODUCT APPROVAL FOR THE
 ROOF SHINGLES.
  
 3.) FBC R 905.1.1.1, CLARIFY THE ROOFING UNDERLAYMENT
 SYSTEM TO BE USED BY INDICATING THE OPTION (2 PLIES OF
 30# FELT OR OTHER OPTION PER FBC R 905.1.1.1) IN
 ADDITION TO THE NOTE ON DETAIL 10 FROM PLAN SHEET A-3
 THAT INDICATES 30# FELT.
  
 4.) FBC B 107.2.1, PLEASE OBTAIN A ROOFING SUB-PERMIT.
  
 5.) FBC EB R502.1, PROVIDE THE ENERGY CALCULATIONS PER
 THE REQUIREMENTS OF THE FLORIDA EXISTING BUILDING CODE.
  
 6.) FBC B 107.2.1, PLEASE CLARIFY THE DIMENSIONS
 REQUIRED FOR THE F-1 FOOTINGS. THE FOOTING SCHEDULE ON
 PLAN SHEET A-4 INDICATES THE F-1 FOOTING DEPTH AT 5",
 THE DETAIL 1/A-4 INDICATES THE DEPTH TO BE 12" BELOW
 4"SLAB. PLEASE CLARIFY THE REQUIRED DEPTH AND CORRECT
 DETAILS TO MATCH.