| BUILDING REVIEW DENIED: |
| |
| FBC B 107.2.1, PROVIDE MORE INFORMATION. PLEASE CLARIFY |
| THE COMPLETE SCOPE OF WORK FOR THIS PROJECT AS IT |
| APPEARS THAT NEW PLAN SHEETS WILL NEED TO INCLUDE THE |
| FOLLOWING: |
| |
| FLOOR PLAN SHOWING THE EXISTING AREA OF CONSTRUCTION |
| AND THE PROPOSED CONSTRUCTION AT THAT AREA INCLUDING |
| NEW WINDOW/DOOR LOCATIONS, PLAN SHEETS SHOWING THE |
| CONNECTION DETAILS FOR ALL OF THE PROPOSED NEW TRUSS TO |
| THE EXISTING TRUSS AND EXISTING STRUCTURAL MEMBERS, |
| PLAN SHEETS WITH DETAILS FOR NEW STRUCTURAL MEMBERS |
| INCLUDING BEAMS/COLUMNS & WALLS, & LOCATION WITH |
| DIMENSIONS OF NEW WINDOWS TO BE INSTALLED. |
| |
| THESE DETAILS AND CALCULATIONS ARE TYPICALLY PUT |
| TOGETHER BY A DESIGN PROFESSIONAL AS THEY NEED TO SHOW |
| THE LOAD CAPACITIES (INCLUDING UPLIFT CAPACITIES) AT |
| THE CONNECTION POINTS. |
| ALL SUBMITTALS BY A DESIGN PROFESSIONAL (ARCHITECT OR |
| ENGINEER) WILL NEED TO BE SIGNED AND SEALED BY THAT |
| DESIGN PROFESSIONAL. |
| |
| ALSO, FOR ENCLOSING AN EXISTING OPEN PATIO AND |
| INCREASING WHAT IS CONSIDERED THE LIVING SPACE, ENERGY |
| CALCULATIONS ARE REQUIRED MEANING THAT ELECTRICAL AND |
| MECHANICAL PERMITS WILL BE NEEDED. |