2023-05-24 10:43:36 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| 1) THERE IS INFORMATION REGARDING THE UNDERLAYMENT BUT, |
| THERE IS NO INDICATION OF A MANUFACTURER'S |
| SPECIFICATION SHEET NOR A PRODUCT NAME FOR THE PROPOSED |
| WOOD FLOORING. |
| |
| WOOD FLOORING IS MANUFACTURED AROUND THE WORLD BUT NOT |
| ALL ARE TESTED AND MEETING LISTED AND NFPA STANDARDS. |
| |
| PER NFPA 101, CH 30 |
| |
| 30.3.3.3 INTERIOR FLOOR FINISH. |
| 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN |
| ACCORDANCE WITH |
| SECTION 10.2. |
| |
| 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH |
| 10.2.2.2 |
| ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL |
| HAVE A |
| MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. |
| |
| FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE WOOD |
| FLOORING NAME AND THE PRODUCT SPEC SHEETS INDICATING |
| THE FIRE BEHAVIOR RATING. |
| |
| IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE, |
| NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC SHEETS |
| WOULD NOT BE REQUIRED. |
| |
| PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL |
| FLOORING, WOOD/VINYL LAMINATES, ETC. |
| |
| |
| |
| 2) THERE ARE INDICATIONS OF NEW WALLS, AS WELL AS, A |
| STATEMENT OF NO FIRE SPRINKLER WORK. |
| |
| ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR |
| CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR |
| FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED |
| CONTRACTORS FOR CODE COVERAGE COMPLIANCE. |
| |
| ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE |
| SPRINKLER SYSTEMS, INCLUDING DEMO, SHALL BE DONE UNDER |
| SEPARATE PERMITS AND SHOP DRAWINGS. |
| |
| THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR |
| FIRE SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE |
| THROUGHOUT THE CONSTRUCTION PERIOD, INCLUDING DEMO. |
| |
| |
| PLEASE REVIEW AND PROVIDE A LETTER FROM A FIRE |
| SPRINKLER CONTRACTOR OR PROVIDE A NOTE OF |
| ACKNOWLEDGMENT TO PROVIDE FIRE SPRINKLER MODIFICATIONS |
| UNDER SEPARATE PERMIT. |
| |
| |
| |
| |
| |
| 3) THERE ARE INDICATIONS OF BATHROOM WORK ON WALLS THAT |
| MAY BE FIRE RATED TENANT OR CORRIDOR SEPARATIONS. |
| |
| ENSURE FIRE RATED TENANT SEPARATION WALLS, IF DAMAGED, |
| ARE REPAIRED TO THE EXISTING FIRE RATED SEPARATION. |
| |
| PROVIDE A NOTE OF ACKNOWLEDGMENT |
| |
| |
| |
| 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |