Plan Review Notes
Plan Review Notes For Permit 23040294
Permit Number 23040294
Review Stop P
Sequence Number 3
Notes
Date Text
2023-06-21 17:30:302ND REVIEW FBC-2020 PLUMBING
 PERMIT- 23040294
 6/21/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES..
 PLEASE NOTE THE REQUESTED RESPONSE TO COMMENTS
 NARRATIVE WAS NOT PROVIDED.
 PLEASE NOTE CONCERNING THE CAR WASH COMMENTS 13-17 THE
 PLANS, DETAILS, SPECIFICATIONS MAY BE DEFERRED
 SUBMITTALS OR SUBMITTED OR UNDER A SEPARATE PERMIT.
 PLEASE ADDRESS THIS ISSUE IN THE NARRATIVE RESPONSE TO
 THE COMMENTS.
  
 1) FAILED. SEPARATE PERMITS ARE REQUIRED FOR THE
 POTABLE WATER BACKFLOW PREVENTER AND THE SAND/OIL
 INTERCEPTOR. AT A MINIMUM, THE PERMIT APPLICATIONS FOR
 EACH SHALL BE SUBMITTED PRIOR TO MAIN PLUMBING PLAN
 APPROVAL. IF CONTRACTORS ARE NOT CURRENTLY SELECTED FOR
 EACH INSTALLATION, PERMIT APPLICATIONS CAN BE SUBMITTED
 TBD (TO BE DETERMINED). EACH COMPLETED APPLICATION
 SHALL BE EMAILED TO [email protected] . YOU WILL
 THEN RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS.
 YOU MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT
 THE APPLICATIONS ARE REQUIRED AT THIS TIME. WE
 RECOMMEND THAT YOU PAY FEES AND UPLOAD PLANS AT THE
 SAME TIME. AFTER YOU HAVE THE PERMIT(S) GENERATED,
 NOTIFY ME VIA EMAIL AND I WILL CHANGE THE REVIEW STATUS
 TO PASS.
  
 9) FAILED. P701: SHOW THE HOT WATER RECIRCULATION LINE
 WILL ALSO MAKE CONNECTION TO THE COLD WATER INLET PIPE
 OR THE HOT WATER RETURN CONNECTION OF THE THERMOSTATIC
 MIXING VALVE- SEC. 607.2.2 FBC P. PLEASE INCLUDE THE
 TMV IN THE EQUIPMENT SCHEDULE ON P001.
  
 PLEASE NOTE THE TMV IS NOT SHOWN IN THE REVISED DETAIL.
  
 10) FAILED. P701: CONCERNING THE SAND/OIL INTERCEPTOR
 UNDER SEPARATE PERMIT PLEASE SUBMIT MANUFACTURER???S
 SPECIFICATIONS INDICATING THE UNIT IS LISTED OR
 LABELED. IF NOT LISTED AND LABELED THE UNIT IN THE
 DETAIL SHALL HAVE AN 18-INCH WATER SEAL AT THE OUTLET
 OPENING AND SHALL HAVE A CAPACITY OF NOT LESS THAN 6
 CUBIC FEET FOR THE FIRST 100 SQUARE FEET OF AREA TO BE
 DRAINED, PLUS 1 CUBIC FOOT FOR EACH ADDITIONAL 100
 SQUARE FEET OF AREA TO BE DRAINED INTO THE SEPARATOR-
 SEC. 1003.4.2- 1003.4.2.2 FBC P.
  
 NOT PROVIDED.
  
 A) FAILED. SUBMIT SPECS FOR THE UNIT AND THE TRAFFIC
 LIDS- SEC. 1003.4.2.
  
 NOT PROVIDED.
  
 B) FAILED. SHOW VENTING FOR THE UNIT- SEC. 1003.9.
  
 NOT PROVIDED.
 P.
  
 13) FAILED. P401 CAR WASH: PLEASE PROVIDE A SCHEDULE
 THAT CORRELATES WITH THE CIRCLED NUMBERS SHOWN ON THE
 PLAN- SEC. 107.2.1 WPB.
  
 NOT PROVIDED.
  
 14) FAILED. P401: PLEASE SUBMIT MANUFACTURER???S
 SPECIFICATIONS FOR THE HOLDING TANKS, AND ACCESS LIDS-
 SECS. 1301.9.2, 1301.9.6 FBC P. PLEASE NOTE THE ACCESS
 LIDS SHALL APPROVED LOCKING DEVICES OR OTHER APPROVED
 METHOD OF SECURING ACCESS. A) REFER TO SEC. 1301.9.9
 AND PROVIDE MARKING AND SIGNAGE DETAILS FOR THE TANKS.
  
 NOT PROVIDED.
  
 15) FAILED. P401: PROVIDE PIPING SPECIFICATIONS FOR THE
 RECLAIM/REUSE SYSTEM- SEC. 1301.6 FBC P.
  
 NOT PROVIDED.
  
 16) FAILED. P401: TO HELP EXPEDITE THE REVIEW PLEASE
 PROVIDE AN ISOMETRIC DRAWING OR PIPING SCHEMATIC FOR
 THE WATER RECLAIM/REUSE SYSTEM- SEC. 1301.4 FBC P.
  
 NOT PROVIDED.
  
 17) FAILED. P401: PROVIDE TANK VENTING DETAILS- SEC.
 1301.9.7 FBC P.
  
 NOT PROVIDED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  