Plan Review Notes
Plan Review Notes For Permit 23040294
Permit Number 23040294
Review Stop M
Sequence Number 2
Notes
Date Text
2023-07-06 10:03:47PLAN DENIED
 1) PROVIDE A COMPLETE ENERGY CALCULATION FOR THE
 PROJECT.
 ONLY SHEETS 1 AND 2 OF 14 WERE SIBMITTED FEC 2020
 C403.2.1
 2) PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATION
 FOR THIS PROJECT FEC 2020 C 403.2.1
 3) PLEASE SHOW ON THE PLAN THE LOCATION OF THE
 CARBON MONOXIDE AND NITROGEN DIOXIDE DETECTORS.
 SECTION 107 FBC.