2023-06-23 11:21:01NEW COMMERCIAL BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE A SOIL REPORT FBC 1803.2
  
 2) ACCESSIBLE RESTROOM - PLEASE SHOW THE TOILET REAR
 GRAB BAR DIMENSIONS WITHOUT THE 6' DIMENSION FROM THE
 SIDE WALL - 604.5.2 REAR WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24
 INCHES (610 MM) MINIMUM ON THE OTHER SIDE.
  
 3) ACCESSIBLE RESTROOM - PLEASE USE THE WORDS
 "REFLECTIVE SURFACE" WHEN SHOWING THE DIMENSIONS FROM
 THE FLOOR TO THE BOTTOM OF THE MIRROR - FBC A 603.3
 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND
  
 4) ACCESSIBLE RESTROOM - THE TOILET VERTICAL GRAB BAR
 IS NOT REQUIRED - PLEASE SHOW THE 12" CLEARANCE ABOVE
 THE HORIZONTAL GRAB BAR - FBC A 609.3 THE SPACE BETWEEN
 THE GRAB BAR AND PROJECTING OBJECTS ABOVE SHALL BE 12
 INCHES (305 MM) MINIMUM.
  
 5) ACCESSIBLE RESTROOM - PLEASE SHOW THE MAXIMUM TOILET
 GRAB BAR HEIGHT TO THE TOP OF THE GRIPPING SURFACE NOT
 TO THE CENTER OF THE BAR - FBC A 609.4 POSITION OF GRAB
 BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE
  
 6) ACCESSIBLE RESTROOM - PLEASE SHOW THE SIZE OF THE
 TOILET STALL DOOR AND THE CLEAR FLOOR SPACE FOR THE
 DOOR MANEUVERING CLEARANCE - FBC A 404.2.3 AND 404.2.4
  
 7) NOT SURE IF THESE ITEMS ARE TO BE DEFERRED - PLEASE
 CLARIFY ON THE DRAWING - PLEASE PROVIDE COMPLETE (FRONT
 PAGES AND THE INSTALLATION INSTRUCTIONS) MIAMI DADE OR
 FLORIDA STATE PRODUCT APPROVALS FOR THE EXTERIOR
 WINDOWS, DOORS, LOUVERS AND ROOFING SYSTEMS - ALL
 PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED
 APPROVED BY THE BUILDING DESIGNER OF RECORD UNLESS
 LISTED ON THE DRAWING BY THE PRODUCT APPROVAL NUMBER -
 FBC 107.3.4
  
 8) PLEASE PROVIDE THE EXTERIOR WALL ALUMINUM COMPOSITE
 PANEL DETAILS - FBC 1609
  
 9) DRAWING C09 SHOWS THE FLOOR ELEVATION AT THE FRONT
 OF THE BUILDING AT 19.00 NAVD AND THE REAR OF THE
 BUILDING AT 18.00 NAVD - DRAWING C-05 SHOWS THE FLOOR
 ELEVATION AT 18.50 - PLEASE SHOW THE FLOOR ELEVATION TO
 MATCH ON ALL DRAWINGS.
  
 10) NEED TO KNOW IF THE "BUILDING" IS IN THE AE 13.4
 FLOOD ZONE - PLEASE SHOW THE DELINEATION LINE BETWEEN
 THE FLOOD ZONES X AND AE 13.4 ON A SURVEY OR THE CIVIL
 PLANS - IF THE BUILDING IS IN THE FLOOD ZONE A PROPOSED
 ELEVATION CERTIFICATE WILL BE NEEDED - FBC WPB 107.3.5
  
 11) ITEMS TO BE DEFERRED SUBMITTALS SHALL BE LISTED ON
 THE CONSTRUCTION DOCUMENTS - FBC WPB107.3.4.1
  
 12) SEPARATE PERMITS ARE REQUIRED FOR BUILDING DEMO,
 PARKING LOT, DUMPSTER ENCLOSURE - PLEASE ACKNOWLEDGE
 THIS.
  
  