Plan Review Notes
Plan Review Notes For Permit 23040294
Permit Number 23040294
Review Stop P
Sequence Number 1
Notes
Date Text
2023-06-20 16:19:041ST REVIEW FBC-2020 PLUMBING
 PERMIT- 23040294
 5/16/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. THESE 1ST REVIEW COMMENTS
 WERE ALSO INSERTED UNDER THE 2ND REVIEW DUE TO A LOCKUP
 IN THE SOFTWARE.
  
 1) SEPARATE PERMITS ARE REQUIRED FOR THE POTABLE WATER
 BACKFLOW PREVENTER AND THE SAND/OIL INTERCEPTOR. AT A
 MINIMUM, THE PERMIT APPLICATIONS FOR EACH SHALL BE
 SUBMITTED PRIOR TO MAIN PLUMBING PLAN APPROVAL. IF
 CONTRACTORS ARE NOT CURRENTLY SELECTED FOR EACH
 INSTALLATION, PERMIT APPLICATIONS CAN BE SUBMITTED TBD
 (TO BE DETERMINED). EACH COMPLETED APPLICATION SHALL BE
 EMAILED TO [email protected] . YOU WILL THEN
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATIONS ARE REQUIRED AT THIS TIME. WE RECOMMEND
 THAT YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME.
 AFTER YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA
 EMAIL AND I WILL CHANGE THE REVIEW STATUS TO PASS.
  
 2) SHEETS P001 & P201B: THE SK-3 SINKS IN THE SERVICE
 FLOOR AREA ARE LISTED AS ADA COMPLIANT IN THE SCHEDULE.
 PLEASE PROVIDE ACCESSIBILITY DETAILS FOR THE SINKS
 INCLUDING CLEAR FLOOR SPACES, SINK HEIGHTS, AND KNEE
 AND TOE CLEARANCES- SEC. 606.2 FBC ACC.
  
 3) P201B, P501: THE SK-3 SINKS ON THE NORTH SIDE OF THE
 SERVICE FLOOR AREA ARE DRAINING INTO THE SANITARY
 HOWEVER THE SK-3 SINK FLOOR DRAINS ON THE SOUTH SIDE
 ARE DRAINING INTO THE SAND/OIL INTERCEPTOR. REFER TO
 SEC. 1003.4 FBC P AND CLARIFY THE PURPOSES OF THE SINKS
 AND THE CONTENT OF DRAINAGE FROM EACH.
  
 4) P201A: PLEASE PROVIDE AN ENLARGED PLUMBING DETAIL
 FOR THE ELEVATOR SUMP PUMP AND PIT IN ACCORDANCE WITH
 SEC. 712.1- 712.3.5 FBC P. PLEASE SEE SEC. 3002.9 FBC B
 AND SHOW THE PUMP DISCHARGE PIPE WILL INDIRECTLY
 CONNECTED TO THE SANITARY DRAINAGE SYSTEM.
  
 5) P301B, P401: PLEASE SHOW THE LOCATION OF THE MAIN
 WATER SHUTOFF VALVE FOR THE CARWASH- SEC. 606.1 FBC P.
  
 6) P001 & P401: PROVIDE AN EQUIPMENT SCHEDULE FOR THE
 RPZ BACKFLOW PREVENTER AT THE CAR WASH SUPPLY LINE-
 TABLE 608.1 FBC P.
  
 7) P501: THE VENT SYSTEM FOR THE MAIN RESTROOMS APPEARS
 TO BE A CLOSED LOOP WITH NO MEANS OF PROVIDING AIR FOR
 CIRCULATION. PLEASE PROVIDE A VENT FOR THE SYSTEM THAT
 EXTENDS TO OPEN AIR OR AN AAV- SEC. 905.1 FBC P.
  
 8) P502: SHOW THE MEANS OF PROVIDING TEMPERED WATER
 DELIVERY FROM THE PUBLIC LAVATORIES- SEC. 419.5 FBC P.
 PLEASE NOTE TEMPERED WATER MIXING VALVES SHALL CONFORM
 TO ASSE 1070- SEC. 607.1.2 FBC P.
  
 9) P701: SHOW THE HOT WATER RECIRCULATION LINE WILL
 ALSO MAKE CONNECTION TO THE COLD WATER INLET PIPE OR
 THE HOT WATER RETURN CONNECTION OF THE THERMOSTATIC
 MIXING VALVE- SEC. 607.2.2 FBC P. PLEASE INCLUDE THE
 TMV IN THE EQUIPMENT SCHEDULE ON P001.
  
 10) P701: CONCERNING THE SAND/OIL INTERCEPTOR UNDER
 SEPARATE PERMIT PLEASE SUBMIT MANUFACTURER???S
 SPECIFICATIONS INDICATING THE UNIT IS LISTED OR
 LABELED. IF NOT LISTED AND LABELED THE UNIT IN THE
 DETAIL SHALL HAVE AN 18-INCH WATER SEAL AT THE OUTLET
 OPENING AND SHALL HAVE A CAPACITY OF NOT LESS THAN 6
 CUBIC FEET FOR THE FIRST 100 SQUARE FEET OF AREA TO BE
 DRAINED, PLUS 1 CUBIC FOOT FOR EACH ADDITIONAL 100
 SQUARE FEET OF AREA TO BE DRAINED INTO THE SEPARATOR-
 SEC. 1003.4.2- 1003.4.2.2 FBC P.
  
 A) SUBMIT SPECS FOR THE UNIT AND THE TRAFFIC LIDS- SEC.
 1003.4.2.
  
 B) SHOW VENTING FOR THE UNIT- SEC. 1003.9.
  
 11) A105 & P203: PROVIDE ROOF DRAINAGE CALCULATIONS FOR
 THE SERVICE DRIVE SECTION OF THE BUILDING AND SCUPPER
 AND OVERFLOW SIZES AND INSTALLATION DETAILS- SEC.
 1106.1 FBC P.
  
 12) A106 & P401: PROVIDE ROOF DRAINAGE CALCULATIONS FOR
 THE CAR WASH BUILDING AND GUTTER AND DOWNSPOUT SIZES-
 SECS, 1106.1, 1106.3 & 1106.6 FBC P.
  
 13) P401 CAR WASH: PLEASE PROVIDE A SCHEDULE THAT
 CORRELATES WITH THE CIRCLED NUMBERS SHOWN ON THE PLAN-
 SEC. 107.2.1 WPB.
  
 14) P401: PLEASE SUBMIT MANUFACTURER???S SPECIFICATIONS
 FOR THE HOLDING TANKS, AND ACCESS LIDS- SECS. 1301.9.2,
 1301.9.6 FBC P. PLEASE NOTE THE ACCESS LIDS SHALL
 APPROVED LOCKING DEVICES OR OTHER APPROVED METHOD OF
 SECURING ACCESS. A) REFER TO SEC. 1301.9.9 AND PROVIDE
 MARKING AND SIGNAGE DETAILS FOR THE TANKS.
  
 15) P401: PROVIDE PIPING SPECIFICATIONS FOR THE
 RECLAIM/REUSE SYSTEM- SEC. 1301.6 FBC P.
  
 16) P401: TO HELP EXPEDITE THE REVIEW PLEASE PROVIDE AN
 ISOMETRIC DRAWING OR PIPING SCHEMATIC FOR THE WATER
 RECLAIM/REUSE SYSTEM- SEC. 1301.4 FBC P.
  
 17) P401: PROVIDE TANK VENTING DETAILS- SEC. 1301.9.7
 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  