Plan Review Notes
Plan Review Notes For Permit 23040294
Permit Number 23040294
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2023-04-27 11:08:00THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A102- THERE IS AN INDICATION OF A FIRE RATED
 WALL ALONG THE SERVICE SHOP WALL THAT SEPARATES THE
 PARTS AREA; HOWEVER, THERE IS NO FIRE RATED WALL ALONG
 THE SERVICE WALL BY THE LOCKER ROOMS & TECH BREAKROOMS.
  
 THERE IS ALSO AN UNPROTECTED 4'8" OPENING ALONG THAT
 WALL.
  
 PER NFPA 101 CH 6, THERE IS REQUIRED SEPARATION OF
 OCCUPANCY AND SEPARATION OF HAZARD.
  
 ONE MAY ATTEMPT TO CALL THAT AREA ACCESSORY TO THE
 SERVICE SHOP BUT THE SERVICE SHOP IS OF HIGHER HAZARD
 AND RATED SEPARATION IS REQUIRED AS INDICATED FROM THE
 PARTS SECTION.
  
 THAT OPENING IS REQUIRED TO BE PROTECTED ACCORDING TO
 THE RATING.
  
 PER NFPA 101, CH 6:
  
 6.2 HAZARD OF CONTENTS
 6.2.1 GENERAL.
 6.2.1.1 FOR THE PURPOSE OF THIS CODE, THE HAZARD OF
 CONTENTS SHALL BE
 THE RELATIVE DANGER OF THE START AND SPREAD OF FIRE,
 THE DANGER OF SMOKE
 OR GASES GENERATED, AND THE DANGER OF EXPLOSION OR
 OTHER OCCURRENCE
 POTENTIALLY ENDANGERING THE LIVES AND SAFETY OF THE
 OCCUPANTS OF THE
 BUILDING OR STRUCTURE.
  
 6.2.1.3* FOR THE PURPOSE OF THIS CODE, WHERE DIFFERENT
 DEGREES OF HAZARD
 OF CONTENTS EXIST IN DIFFERENT PARTS OF A BUILDING OR
 STRUCTURE, THE MOST
 HAZARDOUS SHALL GOVERN THE CLASSIFICATION, UNLESS
 HAZARDOUS AREAS ARE
 SEPARATED OR PROTECTED AS SPECIFIED IN SECTION 8.7 AND
 THE APPLICABLE
 SECTIONS OF CHAPTERS 11 THROUGH 43.
  
 6.2.2 CLASSIFICATION OF HAZARD OF CONTENTS.
 6.2.2.1* GENERAL. THE HAZARD OF CONTENTS OF ANY
 BUILDING OR STRUCTURE
 SHALL BE CLASSIFIED AS LOW, ORDINARY, OR HIGH IN
 ACCORDANCE WITH 6.2.2.2,
 6.2.2.3, AND 6.2.2.4
  
 PLEASE REVIEW AND PROVIDE SPECIFIC DETAILS AND CODE
 REFERENCES OF PROVIDE THE REQUIRED FIRE RATING ALONG
 THE REMAINDER OF THE WALL.
  
  
  
 2) SHEET E201 - THERE IS AN INDICATION OF AN EXIT SIGN
 WITHIN THE CORRIDOR OVER DOOR # 107 LEADING INTO THE
 SERVICE ADVISORS AREA.
  
 THAT DOOR SWINGS AGAINST THE PATH OF TRAVEL.
  
 ALL OTHER EXIT DOORS SWING IN THE PATH OF TRAVEL.
  
 PER NFPA 101, CH 77.2.1.4.2* DOOR LEAF SWING DIRECTION.
 DOOR LEAVES REQUIRED TO BE OF
 THE SIDE-HINGED OR PIVOTED-SWINGING TYPE SHALL SWING IN
 THE DIRECTION
 OF EGRESS TRAVEL UNDER ANY OF THE FOLLOWING CONDITIONS:
 (1) WHERE SERVING A ROOM OR AREA WITH AN OCCUPANT LOAD
 OF 50 OR MORE,
 EXCEPT UNDER ANY OF THE FOLLOWING CONDITIONS:
 (A) DOOR LEAVES IN HORIZONTAL EXITS SHALL NOT BE
 REQUIRED TO SWING
 IN THE DIRECTION OF EGRESS TRAVEL WHERE PERMITTED BY
 7.2.4.3.8.1
 OR 7.2.4.3.8.2.
 (B) DOOR LEAVES IN SMOKE BARRIERS SHALL NOT BE REQUIRED
 TO SWING
 IN THE DIRECTION OF EGRESS TRAVEL IN EXISTING HEALTH
 CARE OCCUPAN CIES, AS PROVIDED IN CHAPTER 19.
 (2) WHERE THE DOOR ASSEMBLY IS USED IN AN EXIT
 ENCLOSURE, UNLESS THE
 DOOR OPENING SERVES AN INDIVIDUAL LIVING UNIT THAT
 OPENS DIRECTLY
 INTO AN EXIT ENCLOSURE
 (3) WHERE THE DOOR OPENING SERVES A HIGH-HAZARD
 CONTENTS AREA
  
 PLEASE REVIEW AND PROVIDE SPECIFIC DETAILS AND CODE
 REFERENCES OR CORRECT THE SWING DIRECTION.
  
  
 3) SHEET FS201 - THERE APPEARS TO BE AB INDICATION OF A
 SINGLE CLASS 1 2 1/2' HOSE CONNECTION IN THE CENTER OF
 THE PARKING GARAGE.
  
 PER NFPA 1
  
 13.2 STANDPIPE SYSTEMS.
 13.2.1 GENERAL. THE DESIGN AND INSTALLATION OF
 STANDPIPE SYS TEMS SHALL BE IN ACCORDANCE WITH SECTION
 13.2 AND NFPA 14,
 STANDARD FOR THE INSTALLATION OF STANDPIPE AND HOSE
 SYSTEMS.
 13.2.2 WHERE REQUIRED.
 13.2.2.1 WHERE REQUIRED BY THIS CODE OR THE REFERENCED
 CODES
 AND STANDARDS LISTED IN CHAPTER 2, STANDPIPE SYSTEMS
 SHALL BE
 INSTALLED IN ACCORDANCE WITH 13.2.1.
 13.2.2.2 NEW BUILDINGS SHALL BE EQUIPPED WITH A CLASS I
 STAND PIPE SYSTEM INSTALLED IN ACCORDANCE WITH THE
 PROVISIONS OF SEC TION 13.2 WHERE ANY OF THE FOLLOWING
 CONDITIONS EXIST:
 (1) MORE THAN THREE STORIES ABOVE GRADE WHERE THE
 BUILDING IS
 PROTECTED BY AN APPROVED AUTOMATIC SPRINKLER SYSTEM
 (2) MORE THAN TWO STORIES ABOVE GRADE WHERE THE
 BUILDING IS
 NOT PROTECTED BY AN APPROVED AUTOMATIC SPRINKLER SYSTEM
 (3) MORE THAN 50 FT (15 M) ABOVE GRADE AND CONTAINING
 INTER MEDIATE STORIES OR BALCONIES
 (4) MORE THAN ONE STORY BELOW GRADE
 (5) MORE THAN 20 FT (6.1 M) BELOW GRADE
  
 PER NFPA 14
  
 7.3 LOCATIONS OF HOSE CONNECTIONS.
 7.3.1* GENERAL.
 7.3.1.1 HOSE CONNECTIONS AND HOSE STATIONS SHALL BE
 UNOB STRUCTED AND SHALL BE LOCATED NOT LESS THAN 3 FT
 (0.9 M) OR MORE
 THAN 5 FT (1.5 M) ABOVE THE FLOOR.
 7.3.1.1.1 THIS DIMENSION SHALL BE MEASURED FROM THE
 FLOOR TO
 THE CENTER OF THE HOSE VALVE.
  
 7.3.2* CLASS I SYSTEMS. CLASS I SYSTEMS SHALL BE
 PROVIDED WITH
 21???2 IN. (65 MM) HOSE CONNECTIONS IN THE FOLLOWING
 LOCATIONS:
 (1) AT THE MAIN FLOOR LANDING IN EXIT STAIRWAYS
 (2) ON EACH SIDE OF THE WALL ADJACENT TO THE EXIT
 OPENINGS OF
 HORIZONTAL EXITS
 (3) IN OTHER THAN COVERED MALL BUILDINGS, IN EACH EXIT
 PAS SAGEWAY AT THE ENTRANCE FROM THE BUILDING AREAS
 INTO THE
 PASSAGEWAY
 (4) IN COVERED MALL BUILDINGS, AT THE ENTRANCE TO EACH
 EXIT
 PASSAGEWAY OR EXIT CORRIDOR, AND AT THE INTERIOR SIDE
 OF
 PUBLIC ENTRANCES FROM THE EXTERIOR TO THE MALL
 (5)*AT THE HIGHEST LANDING OF STAIRWAYS WITH STAIRWAY
 ACCESS TO A
 ROOF, OR ON ROOFS WITH A SLOPE OF LESS THAN 4 IN 12
 WHERE
 STAIRWAYS DO NOT ACCESS THE ROOF
  
 7.3.2.3* HOSE CONNECTIONS ON ONE SIDE OF A HORIZONTAL
 EXIT
 SHALL NOT BE REQUIRED WHERE ANOTHER OUTLET ON THAT SIDE
 OF THE
 HORIZONTAL EXIT CAN REACH THE PORTIONS OF THE BUILDING
 ON THE
 OTHER SIDE OF THE HORIZONTAL EXIT WITHIN THE DISTANCES
 REQUIRED
 BY 7.3.2.3.1 THAT WOULD HAVE BEEN PROTECTED BY THE
 OUTLET THAT
 WAS OMITTED.
 7.3.2.3.1 THIS TRAVEL DISTANCE SHALL BE 200 FT (61 M)
 FOR
 SPRINKLERED BUILDINGS AND 130 FT (39.7 M) FOR NONSPRIN
 KLERED BUILDINGS
  
 PLEASE REVIEW AND PROVIDE HOSE CONNECTION WITHIN THE
 STAIRWELLS.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  