Plan Review Notes
Plan Review Notes For Permit 23040294
Permit Number 23040294
Review Stop B
Sequence Number 1
Notes
Date Text
2023-04-28 10:20:31NEW COMMERCIAL BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE A SOIL REPORT FBC 1803.2
  
 2) DRAWING G005 - DETAIL 4 - SHOWS THE ACCESSIBLE
 PARKING SPACE WIDTH AT 9' - THE MINIMUM ACCESSIBLE
 PARKING SPACE WIDTH IS 12 FEET - FBC A 502.2
  
 3) ACCESSIBLE RESTROOM - PLEASE SHOW THE TOILET REAR
 GRAB BAR DIMENSIONS WITHOUT THE 6' DIMENSION FROM THE
 SIDE WALL - 604.5.2 REAR WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24
 INCHES (610 MM) MINIMUM ON THE OTHER SIDE.
  
 4) ACCESSIBLE RESTROOM - PLEASE USE THE WORDS
 "REFLECTIVE SURFACE" WHEN SHOWING THE DIMENSIONS FROM
 THE FLOOR TO THE BOTTOM OF THE MIRROR - FBC A 603.3
 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND
  
 5) ACCESSIBLE RESTROOM - THE TOILET VERTICAL GRAB BAR
 IS NOT REQUIRED - PLEASE SHOW THE 12" CLEARANCE ABOVE
 THE HORIZONTAL GRAB BAR - FBC A 609.3 THE SPACE BETWEEN
 THE GRAB BAR AND PROJECTING OBJECTS ABOVE SHALL BE 12
 INCHES (305 MM) MINIMUM.
  
 6) ACCESSIBLE RESTROOM - PLEASE SHOW THE MAXIMUM TOILET
 GRAB BAR HEIGHT TO THE TOP OF THE GRIPPING SURFACE NOT
 TO THE CENTER OF THE BAR - FBC A 609.4 POSITION OF GRAB
 BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE
  
 7) ACCESSIBLE RESTROOM - PLEASE SHOW THE SIZE OF THE
 TOILET STALL DOOR AND THE CLEAR FLOOR SPACE FOR THE
 DOOR MANEUVERING CLEARANCE - FBC A 404.2.3 AND 404.2.4
  
 8) PLEASE SHOW THE ADVISORS SERVICE DESK HEIGHT AND
 CLEAR FLOOR SPACE TO COMPLY WITH FBC A 904.4
  
 9) PLEASE SHOW THE CUSTOMER AND EMPLOYEE PARKING AREAS
 IF THEY ARE IN THE GARAGE PLEASE SHOW THE ACCESSIBLE
 PARKING SPACES PER FBC A 208.3
  
 10) PLEASE SHOW THE ROOF HEIGHT TO THE TOP OF THE
 ELEVATOR/STAIR SHAFT - FBC 504.1
  
 11) DRAWING A 321 - DETAIL 5 SHOWS THE ROOF DECK AT 34'
 5" AND THE TOP OF THE PARAPET AT 37' 9" - PLEASE SHOW
 THE REQUIRED GUARD - FBC 1015.2
  
 12) PLEASE SHOW THE DIMENSIONS FROM THE 2ND FLOOR DECK
 TO THE BOTTOM OF THE 2ND FLOOR WALL OPENINGS - 1015.2
 WHERE REQUIRED.
 GUARDS SHALL BE LOCATED ALONG OPEN-SIDED WALKING
 SURFACES, INCLUDING MEZZANINES, EQUIPMENT PLATFORMS,
 AISLES, STAIRS, RAMPS AND LANDINGS THAT ARE LOCATED
 MORE THAN 30 INCHES (762 MM) MEASURED VERTICALLY TO THE
 FLOOR OR GRADE BELOW AT ANY POINT WITHIN 36 INCHES (914
 MM) HORIZONTALLY TO THE EDGE OF THE OPEN SIDE. GUARDS
 SHALL BE ADEQUATE IN STRENGTH AND ATTACHMENT IN
 ACCORDANCE WITH SECTION 1607.8.
  
 13) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, DOORS,
 LOUVERS AND ROOFING SYSTEMS - ALL PRODUCT APPROVALS
 NEED TO BE REVIEWED AND MARKED APPROVED BY THE BUILDING
 DESIGNER OF RECORD UNLESS LISTED ON THE DRAWING BY THE
 PRODUCT APPROVAL NUMBER - FBC 107.3.4
  
 14) PLEASE PROVIDE THE EXTERIOR WALL ALUMINUM COMPOSITE
 PANEL DETAILS - FBC 1609
  
 15) PLEASE PROVIDE THE PRE CAST CONCRETE WALL
 CONNECTION DETAILS - FBC 1609
  
 16) PLEASE PROVIDE THE PRE CAST DOUBLE TEE CONNECTION
 DETAILS - FBC 1609
  
 17) ITEMS TO BE DEFERRED SUBMITTALS SHALL BE LISTED ON
 THE CONSTRUCTION DOCUMENTS - FBC WPB107.3.4.1
  
  