Plan Review Notes For Permit 23040249 |
Permit Number |
23040249 |
|
Review Stop |
B |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2023-06-15 09:45:39 | ROOF OVER | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) THE DRAWINGS SHOW A WIND PRESSURE FOR WIND ZONE 3' | | AS (-152) - THE ROOF PANEL PRODUCT APPROVAL SHOWS A | | MAXIMUM WIND DESIGN PRESSURE OF (-142) WHICH IS LOWER | | THAN THE PRESSURE ON THE DRAWING - PLEASE CLARIFY HOW | | THIS MEETS REQUIREMENTS PER FBC 1609 |
|